Download Print this page

Honeywell ALL-SPEC Installation Instructions Manual page 3

Air sampling smoke detection system

Advertisement

Detector Module Settings
In the following tables the switch S1 has two positions:
on
off
The standard settings have a grey background.
Setting the response sensitivity
detector module
DM-TP-
DM-TP-
DM-TP-
50
10
01
0,8 %/m
0,12 %/m
0,4 %/m
0,06 %/m
0,2 %/m
0,03 %/m
1,0 %/m
0,5 %/m
0,1 %/m
0,015%/m
Setting the alarm delay
0 seconds
10 seconds
30 seconds
60 seconds
Setting the activating threshold
"air flow fault"
I
II
III
IV
Setting the delay
"air flow fault"
0.5 minutes
2 minutes
15 minutes
60 minutes
Setting the fault signal
non-latched
latched
⋅ SENS
Setting LOGIC
ALL-SPEC_Unit_HON.doc
on
on
off
on
on
off
off
off
S1. 3
S1. 4
off
off
on
off
off
on
on
on
S1. 5
S1. 6
on
off
off
on
off
off
on
on
S1. 7
S1. 8
off
on
on
off
on
on
off
off
S1. 9
off
on
S1.10
off
off
on
on
07/2011
3/9

Advertisement

loading