3. Piping work and refrigerant charge
3.3.3  Piping system for line branch
OU
IU
IVX Premium
quantity
IVX Standard
allowed

 
Maximum refrigerant piping length (Line branch system)
IVX Premium series
Outdoor Unit
Maximum piping length between the
outdoor unit and the farthest indoor unit
Maximum piping length from first branch to each indoor unit (L2)
Maximum piping length from branch to indoor unit (L3)
Total piping length L4 + (L3
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
Maximum height Difference Indoor / Indoor
Maximum height difference:
Branch pipe/Indoor
Branch pipe/branch pipe
IVX Standard series
Outdoor Unit
Maximum piping length between the
outdoor unit and the farthest indoor unit
Maximum piping length from first branch to each indoor unit (L2)
Maximum piping length from branch to indoor unit (L3)
Total piping length L4 + (L3
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
Maximum height Difference Indoor / Indoor
Maximum height difference:
Branch pipe/Indoor
Branch pipe/branch pipe
65
3 HP
4 HP
2 -3
2 - 5
--
Actual Length (L1)
Equivalent Length (EL)
+L3
+L3
....)
1
2
3
Actual Length (L1)
Equivalent Length (EL)
+L3
+L3
....)
1
2
3
SMGB0079 rev.0 - 01/2013
5 HP
6 HP
8 HP
2 - 6
2 - 4
3HP
4HP
5HP
50
75
70
95
20
30
10
60
95
4HP
5HP
6HP
70
75
90
95
20
10
70
75
10 HP
12 HP
2 - 8
(picture is as example)
(m)
6HP
8HP
10HP
12HP
100
125
40
15
100
145
30 / 20
10
3
(m)
8HP
10HP
12HP
100
125
25
15
100
145
30 / 20
3
3
3