12. Maintenance notes
12.1.5  Alarm code "31"
Question and answer for the field work
Example 4: Alarm code "31"
Phenomenon
Alarm code "31" sometimes occurred and the system stopped.
The combination of the indoor units and the outdoor unit was the following.
Cause
This system was used in a tenant building. One of tenant's customers turned off the main switch for the indoor unit while
other indoor units are running. This results in a different setting of the total indoor unit capacity in the same refrigerant
cycle.
Countermeasure
All the main switches for the indoor units were always ON.
12.1.6  Not cooling well due to insufficient installation space for the outdoor unit
Question and answer for the field work
Example 5: Not cooling well due to insufficient installation space for outdoor unit
Cooling operation was well performed through the intermediate season. However the cooling operation was not well avai-
Phenomenon
lable when the outdoor temperature was higher than 35 °C.
As the outdoor units were installed without a sufficient installation space the hot discharge air from other outdoor units was
circulated.
In this case though the outdoor temperature was 35 °C the actual suction air temperature was nearly 50 °C and protection
Cause
system from excessively high suction pressure was activated the frequency of the compressor was decreased and the
cooling capacity was also decreased accordingly.
As the outdoor units in-line were installed back to back with a distance of 600 mm between each outdoor unit's back the
hot discharged air from other outdoor units was circulated.
Countermeasure
Ensure that sufficient space should be secured for multi-row and multiple-installation.
Example
N O T E
If L is larger than H mount the units on a base so that H is greater or equal to L.
In this situation ensure that the base is closed and does not allow the airflow to short circuit.
When the mark * dimension is secured be sure to mount the airflow guide.
458
SMGB0079 rev.0 - 01/2013
Power
Source
ON
ON
OFF
ON
ON
Keep a distance of more than 15 mm between other units
and do not put obstacles on the right and left sides. Dimen-
sion B is as shown below.
For detailed information please refer to
chapter.
L
0 < L < 1/2H
1/2H < L < H
ON
Unit Installation
A
B
600 or more
300 or more
1400 or more
350 or more