Hitachi Universal Storage Platform VM Installation Planning Manual page 38

Hide thumbs Also See for Universal Storage Platform VM:
Table of Contents

Advertisement

Primary Rack – Power connection specifications
CB
CB
PDU
PDU
CB
CB
PDP1
• When connected correctly to the Power Distribution Panels
(PDP), in the event that one PDP fails, two PDUs will
continue to receive power and will supply sufficient power
to all components in the rack
• The power to the SBX-Chassis is supplied from the Control
Frame
2–22
Hitachi Universal Storage Platform VM Installation Planning Guide
CORRECT Power Connections to
Primary Rack
Primary Rack
DKU-R1
Disk Chass is
PS30
x 15
PS31
PS20
x 15
PS21
x 15
PS10
PS11
x 15
PS00
PS01
DKU-R0
Disk Chass is
x 15
PS30
PS31
x 15
PS20
PS21
x 15
PS10
PS11
x 15
PS00
PS01
SBX-Chassis
DKC
Cont rol F ram e
CL1
CL2
PS11
PS12
PS21
PS22
Connected to
AC Input Line
same PDP
Duplex Structure
Breaker
Figure 2-12: Direct Power Connection
Installation Requirements
INCORRECT Power Connections to
Primary Rack
Primary Rack
PS30
PS20
PS10
CB
CB
PS00
PS30
CB
CB
PS20
PS10
PDU
PDU
PS00
PDU
PDU
CB
CB
CL1
PS11
CB
CB
PDP2
PDP1
• When connected incorrectly to the PDPs, the failure of one
PDP will result in insufficient power being supplied to the
components in the rack.
DKU-R1
Disk Chassi s
x 15
PS31
x 15
PS21
x 15
PS11
CB
x 15
PS01
DKU-R0
Disk Chassi s
x 15
PS31
CB
x 15
PS21
x 15
PS11
PDU
x 15
PS01
PDU
SBX-Chassis
DKC
Co ntro l Fram e
CB
CL2
PS12
PS21
PS22
CB
PDP2

Advertisement

Table of Contents
loading

Table of Contents