ZonePRO
Applications
®
Stand Alone VAV Pressure
Dependent (VVT Zoning) Control
• Typical building applications include zoning for office
buildings, airports, strip-malls and multi-tenant facilities
that have multiple terminal zones that run off of a single
air-handler.
• Thermostats provide modulating control (floating or
analog) for each zone.
• Can be configured for cool only, heat only or
auto changeover. Up to 2 re-heat outputs are available
if the discharge air from the air handler needs to be
heated at the zone. (B models)
• Remote sensors are compatible with all ZonePRO
models if remote room sensing or return air
temperature sensing is desired.
• May also be used at the air handler to control the
temperature of the fresh air supply or provide limited
cooling using outdoor air when appropriate.
• All ZonePRO thermostats come with energy-saving
range stop and night setback configurability.
tb7980b1005: Cooling only Pressure Dependent VaV Zone reheat and electric baseboard Heat
®
Supply Air Temperature Sensor
Modulating Damper
Actuator
Hot Water
Coil
R841
Electric Baseboard Heat
Relay
Hydronic Control &
Modulating Heating
• Can be used for modulating hydronic heating or
cooling applications.
• Other common applications include radiant panel
heaters, cabinet heaters, fin-tube radiators and other
electric or hydronic re-heat applications.