Outdoor Power Circuit Board; Brief Check Of Dip-Ipm And Dip-Pfc; Connect To The Outdoor Controller Circuit Board (Cn2) - Mitsubishi Electric PUHZ-SW40VHA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-SW40VHA:
Table of Contents

Advertisement

Outdoor power circuit board

PUHZ-SW40VHA
PUHZ-SW40VHA-BS
PUHZ-SW50VHA
PUHZ-SW50VHA-BS
LD1-LD2
280-380V DC
Connect to
the outdoor
controller
circuit board
(CNDC)
CN2

Connect to the outdoor controller circuit board (CN2)

1-5: Outdoor power circuit board
to the outdoor controller circuit board (0-5V DC)
2-5: Zero cross signal (0-5V DC)
3-4: Not used
[
1, 2, 6, 7 : +
6-5: 16V DC
7-5: 16V DC
OCH525

Brief Check of DIP-IPM and DIP-PFC

W Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.). If they
are short-circuited, it means that they are broken.
1. Check of DIP-IPM
2. Check of DIP-PFC
Note: The marks, L , N , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
Transmitting signal
]
5 : –
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
P1 - L , P1 - N , L - N1 , N - N1
R, S
Connect to the ACL
230V AC
P1
N
L
N2
W
CN3
CN4
Thermistor
Connect from the
<Heatsink>
outdoor controller
(TH8)
circuit board
(CN4)
41
U, V, W
Connect to the compressor (MC)
Voltage among phases: 5V to 180V AC
N1
N1
V
U
P2
CN5
Primary current detection
(Connect to the outdoor
noise filter circuit board
(CN5))
DIP-PFC
DIP-IPM