Step
9
Use a torque wrench to gradually tighten nuts to torque rating shown in Table 42 in sequence
shown in following illustration. Tighten head bolts in stages of 1/3 full torque, 2/3 full torque,
and then full torque.
10
Feed flex tape on new meter body through neck of housing and screw new meter body into
housing until bottom of header portion of center section is approximately flush with neck of
electronics housing.
11
Tighten outside set screw to be sure it is fully seated in slot in header. Loosen set screw half
turn, rotate housing to desired position and tighten set screw.
12
Reverse actions in Steps 2 and 3 in Table 43, as applicable, to return PWA and bracket to
transmitter housing.
We recommend that you lubricate end-cap O-ring with silicon grease such as Dow Corning
#33 or equivalent before you replace end cap.
13
Recalibrate transmitter. Refer to Section 10 for proper procedure.
ATTENTION
Be sure to orient Local Smart Meter for proper viewing through end-cap window. You can
rotate the meter mounting orientation in 90 degree increments.
14
Return transmitter to service and turn ON power
15
Verify transmitter's configuration data. Restore saved database, if applicable.
10/05
Always tighten head bolts in
sequence shown and in these
stages:
1. 1/3 full torque
2. 2/3 full torque
3. Full torque
ST 3000 HART Transmitter Release 300 User Manual
9— Maintenance - Replacing Meter Body
Action
1
3
4
2
22519
105