Honeywell VisionPRO IAQ Product Data page 15

Total home comfort system
Hide thumbs Also See for VisionPRO IAQ:
Table of Contents

Advertisement

ISU
Parameter
Installer Setup
Number
Name
345
Dual Fuel Heat
Pump Control
346
Dual Fuel Heat
Pump Upstage to
Furnace Timer
350
Heat Pump
Balance Point
(also compressor
lockout)
Temperature
360
Heat Pump
Auxiliary Heat
Lockout
Temperature
365
Discharge Temp
Sensor
366
Zoning High
Temperature
Limit
367
Zoning Low
Temperature
Limit
368
Staging
Discharge
Temperature
High Limit
369
Staging
Discharge
Temperature
Low Limit
370
Indoor Humidity
Sensor
372
Indoor
Humidification
Control
Table 3. Installer Setup Menu. (Continued)
Settings
(Factory Defaults Shown in Bold)
0
Balance point only
1
Balance point plus 2° droop
2
Balance point/auxiliary heat lockout plus 2° droop.
0
Disabled
30
30 minutes
45
45 minutes
60
60 minutes
75
75 minutes
0
No heat pump compressor lockout
5
-15
5°F
-15.0°C
10 -12
10°F -12.0°C
15 -9.5
15°F -9.5°C
20 -6.5
20°F -6.5°C
25
-4
25°F -4.0°C
30
-1
30°F -1.0°C
35 1.5
35°F 1.5°C
40 4.5
40°F 4.5°C
45
7
45°F 7.0°C
50
10
50°F 10.0°C
55
13
55°F 13.0°C
60 15.5
60°F 15.5°C
(Show 1/2 degree C)
0
No heat pump auxiliary lockout
5
-15
5°F
-15.0°C
10 -12
10°F -12.0°C
15 -9.5
15°F -9.5°C
20 -6.5
20°F -6.5°C
25
-4
25°F -4.0°C
30
-1
30°F -1.0°C
35 1.5
35°F 1.5°C
40 4.5
40°F 4.5°C
45
7
45°F 7.0°C
50
10
50°F 10.0°C
55
13
55°F 13.0°C
60 15.5
60°F 15.5°C
65 18.5
65°F 18.5°C
(Show 1/2 degree C)
0
None
1
Remote
E
Auto Discover
160
160°F (71°C)
0
Disabled
110–170
110°F to 170°F (43.5°C to 76.5°C)
40
160°F (71°C)
0
Disabled
35-50
35°F to 50°F (1.5°C to 10°C)
110
110°F (43.5°C)
0
Disabled
80-130
80°F to 130°F (26.5°C to 54.5°C)
55
55°F (13°C)
0
Disabled
50-60
50°F to 60°F (10°C to 15.5°C)
0
Disabled
1
Internal—sensor in thermostat
2
Remote
E
Auto Discovered
0
Off
1
Humidify with no Frost Protection
3
Humidify with Frost Protection
E
Auto Discover
VISIONPRO
See Dual Fuel Heat Pump control on page 22.
See Dual Fuel Heat Pump control on page 22.
Only shown for heat pump applications with an
outdoor temperature sensor present.
Only shown for heat pump applications with an
outdoor temperature sensor present.
Only Shown if ISU110 = 1 (Master Zone Controller)
and Discharge Temperature Sensor is available.
Only Shown if ISU110 = 1 (Master Zone Controller)
and Discharge Temperature Sensor is available.
Only Shown if ISU110 = 1 (Master Zone Controller)
and ISU174 = 2 or more. Must have Discharge
Temperature Sensor present.
Only Shown if ISU110 = 1 (Master Zone Controller)
and ISU176 = 2. Must have Discharge Temperature
Sensor present.
If there is a remote sensor installed and the setting is
either auto discover or "remote" the internal thermostat
humidity sensor is disabled. If set to "internal" the
internal thermostat sensor is presented on the screen.
If set to "disabled" the internal sensor and any remote
sensors are disabled, there will be no humidity
displayed and will have no humidification/
dehumidification control.
Shown only if ISU370 = 1, 2 or E.
15
®
IAQ TOTAL HOME COMFORT SYSTEM
Notes
68-0287—1