TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS
CAUTION
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing
the thermostat.
Short circuit or wrong wiring may permanently damage the thermostat or the equipment.
Anti-short cycling can be set to 0 minutes for equipment that has an anti-cycling timer. Do not set to 0 unless the
equipment has an internal anti-cycling timer or damage to equipment can occur.
All TB7600 Series thermostats are to be used only as operating controls. Whenever a control failure could lead
to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/
or alarm system to protect against such catastrophic failures.

Thermostat Installation

1. Open up by pulling on the bottom side of thermostat.
(Fig. 2)
2. Remove wiring terminals.
3. Open the thermostat PCB to the left by pressing the PCB
retaining tabs. (Fig. 3).
4. Pull cables 6 inches out of the wall.
5. Thread cable through the central hole of the base.
6. Align the base and mark the location of the two mounting
holes on the wall. Install proper side of base up.
7. Install anchors in the wall.
8. Insert screws through the mounting holes on each side of
the base and mount base on wall. (Fig. 3).
9. Gently swing back the circuit board back to the base and
push on it until the tabs lock it in place.
10. Strip each wire 1/4 inch.
11. Wire the terminals. See Table 1 for terminal descriptions
and wiring diagram.
12. Gently push back excess cable into hole.
13. Install wiring terminals in correct location (Fig. 4).
14. Reinstall the cover (top first).
15. Install security screw on the bottom, center of the thermo-
stat cover.
62-2016—05
Fig. 2. Remove cover of thermostat
Fig. 3. Location of PCB retaining tabs and
TOP LEFT
5 POLE
CONNECTOR
BOTTOM
8 POLE
CONNECTOR
4
M21300
mounting screws
Fig. 4. Terminal blocks
PCB
RETAINING
TABS
PCB
RETAINING
TABS
M21301
TOP RIGHT
3 POLE
CONNECTOR
M21302