Honeywell remote space sensors installation instructions

Advertisement

T7047C,G,H REMOTE SPACE SENSORS
RESISTANCE
(OHMS)
1000
900
800
700
600
500
10
20
30
40
-10
0
TEMPERATURE (DEGREES)
Fig. 6. T7047G1000 Remote Sensor resistance
change with change in temperature.
RESISTANCE
(OHMS)
1400
1317
1231
1145
1093 OHMS AT
1059
75 F (24 C)
973
20
40
60
80
-7
10
0
20
30
TEMPERATURE (DEGREES)
Fig. 7. T7047H1008 Remote Sensor resistance
change with change in temperature.
Wiring
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Fig. 8 through 16 show schematics and typical
connections. Also refer to instructions supplied with other
system components.
IMPORTANT
To avoid electrical interference, which can
cause erratic performance, keep wiring runs as
short as possible and do not run wires adjacent
to the line voltage electrical distribution
systems. Use shielded cable (Belden type 8762
or equivalent for 2-wire and Belden type 8772 or
equivalent for 3-wire). The cable shield must be
grounded only at the controlled equipment
case.
62-0179
710 OHMS AT
75 F (24 C)
100
50
60
70
80
90
20
30
10
100
120
180
140
160
40
50
70
80
90
60
T7047C
t
F
110
C
40
Fig. 8. Internal schematic and typical
M5354
Fig. 9. T7047C1025 connected to W960 or W927
panel with internal setpoint adjustment.
F
200
220
C
100
M10020
Fig. 10. Two T7047C1025 Sensors and one
temperature-averaging network for a
Fig. 11. Typical wiring for T7047H1008 to
4
W
R
B
T
T
wiring for T7047C1009.
T7047C
T
t
T
Q7300
T
T
T7047C
T
T
T7047G1000
T7047C
T
T
T7047G1000 Sensor providing a
T7300/Q7300 Thermostat/Subbase.
EXCEL 500/100/80
CONTROLLER
A1
A1
T7047H
Excel 80/100/500/600 Controller.
S963B1003
REMOTE SETPOINT
POTENTIOMETER
M7044 OR
M7045 MOTOR
4
T1
TO 24V
1
POWER
SUPPLY
T2
T1
M3383
W960 OR
W927 PANEL
T1
T2
M3386
T
T
M3418
COMMON
M10019

Advertisement

loading