Checkout; Calibration - Honeywell C7189U Installation Instructions Manual

Remote indoor sensor (use with visionpro thermostats)
Table of Contents

Advertisement

Available languages

Available languages

C7189U REMOTE INDOOR SENSOR

CHECKOUT

For best results, allow the sensor to absorb the air
moving through the room for a minimum of twenty
minutes before taking a resistance measurement.
1. Use an accurate thermometer (+/-1ºF[0.5ºC]) mea-
sure the temperature at the sensor location.
2. Remove one wire from one of the sensor's wiring
terminals. Use an ohmmeter to measure the resis-
tance across the sensor. Verify the sensor accu-
racy with the temperature/resistance in Table 1.

CALIBRATION

The sensor is calibrated at the factory and cannot be
recalibrated in the field.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://yourhome.honeywell.com
® U.S. Registered Trademark
© 2005 Honeywell International Inc. Patents Pending.
69-1710EFS-1
M.S. Rev. 10-05
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
Table 1. Sensor Resistance at Room Temperature.
Room Temperature
°F
40
4.4
42
5.6
44
6.7
46
7.8
48
8.9
50
10.0
52
11.1
54
12.2
56
13.3
58
14.4
60
15.6
62
16.7
64
17.8
66
18.9
68
20.0
70
21.1
72
22.2
74
23.3
76
24.4
78
25.6
80
26.7
82
27.8
84
28.9
86
30.0
88
31.1
90
32.2
92
33.3
94
34.4
96
35.6
98
36.7
100
37.8
Ohms of
°C
Resistance
22537
21516
20546
19626
18754
17926
17136
16387
15675
14999
14356
13743
13161
12607
12081
11578
11100
10644
10210
9795
9398
9020
8659
8315
7986
7672
7372
7086
6813
6551
6301