Honeywell Tradeline C7089A Installation Instructions
Honeywell Tradeline C7089A Installation Instructions

Honeywell Tradeline C7089A Installation Instructions

Outdoor sensor

Advertisement

Quick Links

APPLICATION
The C7089 Outdoor Sensor is used with the PC8900
Perfect Climate Comfort Center™ Control System and the
W8900 Remote Module. It senses the outdoor tempera-
ture for display on the PC8900 at the touch of a key. The
sensor is encapsulated to protect against water and
contaminants, and includes 60 in. leadwires.

SPECIFICATIONS

Operating Ambient Temperature Range:
-40 to 128 F (-40 to 53 C)
Operating Relative Humidity:
5% to 95% noncondensing
Dimensions in inches (millimeters):
2-1/4 (57) x 3/8 (10) with 60 (1524) leadwires
®U.S. Registered Trademark
Copyright © 1995 Honeywell Inc. • All Rights Reserved
C7089A Outdoor Sensor
INSTALLATION
When Installing this Product...
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Disconnect power supply before connecting wiring
to prevent electrical shock or equipment damage.
Location and Mounting (Fig. 1)
Mount the sensor where:
• setting can not be tampered with.
• there is good air circulation.
• it can measure the true outdoor ambient
temperature.
• surface is flat.
• the wire distance between the C7089 and W8900 is
less than 200 feet.
Do not mount the sensor:
• in the direct sunlight.
• where hot or cold air blows on the sensor. Discharge
line from an outdoor compressor unit, vent or fan will
cause inaccurate temperature readings.
• where snow, ice or debris can cover it.
Use the following steps to mount the sensor:
Remove the sensor from the mounting clip.
Mark the area on the surface where the C7089
mounting clip will be mounted.
Mount the clip.
X-XX UL
INSTALLATION INSTRUCTIONS
69-0896-1

Advertisement

loading

Summary of Contents for Honeywell Tradeline C7089A

  • Page 1: Specifications

    Use the following steps to mount the sensor: Remove the sensor from the mounting clip. Mark the area on the surface where the C7089 mounting clip will be mounted. Mount the clip. ®U.S. Registered Trademark 69-0896-1 Copyright © 1995 Honeywell Inc. • All Rights Reserved X-XX UL...
  • Page 2 C7089 OUTDOOR SENSOR CAUTION Disconnect the power supply before connecting the wiring to prevent electrical shock or equipment damage. Wiring must comply with applicable codes, ordinances and regulations. Wire the C7089 Outdoor Sensor to the terminals marked OUT on the W8900 Remote Module. If the leadwire provided with the C7089 is not long enough, run cable to a hole at the selected C7089 location.
  • Page 3 3679 to 3655 48.9 3703 to 3679 51.7 3728 to 3703 3752 to 3728 54.4 57.2 3776 to 3752 60.0 3800 to 3776 62.8 3824 to 3800 65.6 3849 to 3824 M6358 Fig. 3. C7089A sensor resistance vs. temperature performance characteristics. 69-0896—1...
  • Page 4 Fig. 4. Outdoor temperature display on the PC8900. Home and Building Control Home and Building Control Honeywell Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario M1P 2V9 69-0896—1...