Honeywell HE420A Owner's Manual page 7

Steam power humidifier
Hide thumbs Also See for HE420A:

Advertisement

APPENDIX A
PROBLEM
Humidifier does not
• Confirm the outdoor temperature sensor is
operate in "Test"
mode.
• Check wiring diagram (Figure 1) for correct
• Check the voltage at the humidistat "24 VAC"
• Ensure the control knob has not been left in the
Humidifier only
• Check the resistance of the sensor by removing
operates in "Test"
mode.
• For automatic applications, make sure the
• If the outdoor temperature sensor is mounted in
Humidifier operates
• Check the humidistat setting. If the RH in the
constantly.
• In "Test" mode, verify that the humidifier will shut
• Check the resistance of the sensor.
• See previous Problem/Solution, regarding
• Turn the humidistat "OFF" and observe whether
Humidifier or
• Use a voltmeter to check for steady 22-30 VAC.
compensating
• Make sure the outdoor temperature sensor
humidistat "chatters"
or clicks on and off
rapidly.
Furnace or heat
• It may be necessary to make a setting change on
pump blower system
runs continuously;
condensation is
• Consult the furnace/heat pump operating manual
building up in
ductwork.
Table 3. Compensating Humidistat Troubleshooting Guide.
SOLUTION
connected to the correct terminals on the
humidistat. (For manual operation, ensure the
jumper pins are positioned correctly.)
installation.
terminals. (Should be 22-30 VAC.)
"Test" position.
the leads from the humidistat terminals and
measuring the resistance across the wires with
an ohmmeter. Compare the reading to the
temperature/resistance chart (right).
outdoor temperature sensor is mounted
completely outside the house (i.e. not recessed
into the hole) on the North, Northeast or
Northwest side, away from direct sunlight. And is
mounted at least 3 feet away from all exhaust
vents.
the fresh air intake duct, make sure the probe is
no further than 30 inches from an outside wall.
home is less than the knob setting, the humidifier
will operate until the humidity level is higher than
the knob setting.
off after approximately one minute.
outdoor temperature sensor mounting locations.
the humidifier turns off. If operation continues,
check Figure 1 wiring diagram. Remove the
wires from the humidistat's "OUT" terminals. If
humidifier continues to operate, check the
humidifier.
wiring does not run alongside the wires carrying
high voltage (120 VAC or higher).
the furnace or heat pump board to prevent the
blower from shifting down to lowest idling speed.
or contact the manufacturer for procedures to
prevent low air flow.
HE420A STEAM POWER HUMIDIFIER
Temp/Resistance Chart
100°F
90°F
80°F
70°F
60°F
50°F
40°F
30°F
20°F
10°F
0°F
-10°F
-20°F
-30°F
Notes:
In automatic applications, if the outdoor
temperature is greater than +50°F (+10°C)
or less than -32°F (-35.6°C), the
compensating humidistat will not operate
(except in "Test" mode).
In both automatic and manual applications,
if the relative humidity in the home is
higher than the knob setting, the
humidistat will not operate. Similarly, the
humidistat will not operate if the indoor RH
exceeds 45%.
7
NOTES
6000 ohms
38°C
7500 ohms
32°C
9500 ohms
27°C
11,500 ohms
21°C
14,000 ohms
16°C
18,000 ohms
10°C
23,000 ohms
4°C
28,500 ohms
-1°C
37,000 ohms
-7°C
46,500 ohms
-12°C
61,500 ohms
-18°C
78,500 ohms
-23°C
105,500 ohms
-29°C
135,000 ohms
-34°C
69-1108—2