Ignition Cable - Honeywell Y343B1002 User Manual

Direct spark gas burner ignition package
Table of Contents

Advertisement

FIG. a--NORMAL
SYSTEM SEQUENCE OF OPERATION.
SERVICE
l
Only persons
trained
and experienced
in DSI
systems should service this equipment.
If a condition
exists
that
causes
the S87D
electronic
module
to go into safety
lockout,
meter
readings
must be taken
quickly
after
restart -
within trial-for-ignition
period.
Always de-energize
the system for at least 30
seconds before recycling for further tests.
The S87D electronic
module
cannot
be re-
paired.
If the troubleshooting
procedure
in-
dicates
a malfunction
in the S87, it must be
replaced.
The following
service
procedures
are for the
S87 and basic
DSI systems.
On all installa-
tions,
refer
to the appliance
manufacturer's
service instructions.
1.
2.
3.
4.
5.
IMPORTANTLY
PRELIMINARY
CHECK
The following
checks
should
be made before trou-
bleshooting
the system.
1. Check for power to the heating appliance
and the
S87D.
2. Check fuse on S87D electronic
module
and re-
place if blown.
3. Make certain that the manual shutoff gas cock in
the supply
line and on the combination
gas control
valve are open.
4. Make certain that all wiring connections
are clean
and tight.
5. Make
certain
the S87 is not in safety
lockout.
De-energize
the system
by moving
the thermostat
set
point below room temperature.
Wait at least 30 seconds
and re-energize
the system
by moving
the thermostat
set point 5 F [2.8 C] above room temperature.
6. Check
ceramic
insulator
on flame
sensor
and
spark
igniter.
A cracked
insulator
will allow current
to
leak to ground.
Replace device if insulator
is cracked.
7. Check the flame sensor and its mounting
bracket.
Correct the position if bent out of shape.
8. Review the S87 normal
sequence
of operation.
See START SYSTEM section.
S87D COMPONENT
CHECKS
SPARK
IGNITION
CIRCUIT
The step-up
transformer
in the S87 provides
spark
ignition
at 15,000 volts
(open
circuit).
To check
the
spark ignition circuit, proceed
as follows:
1. Shut off gas supply to the gas control.
2. Disconnect
the ignition
cable
at the S87 stud
terminal
to isolate
the circuit
from
the spark-igniter.
Prepare
a short jumper
wire, using heavily
insulated
wire such as ignition cable.
very
high
voltage
circuit
and
electrical
shock
3. Perform
this test immediately
upon
energizing
the system -- before the S87D goes into safety lockout
and interrupts
the spark circuit.
Touch one end of the
jumper
firmly
to the 587
GND terminal.
(DO NOT
remove
the existing
ground
lead.)
Slowly
move
the
other end of the jumper
wire toward
the stud terminal
on the S87 to establish
a spark. Pull the wire away from
the stud and note the length
of gap at which
spark
discontinues.
4. A spark
length
of l/8
in. [3.2 mm]
or more
indicates
satisfactory
voltage
output.
If no arc can be
established
or the maximum
spark is less than l/8
in.
[3.2 mm], and power
to the S87 input terminals
was
proved,
replace the S87.
IGNITION CABLE
Check the electrical
continuity
of the ignition
cable
and make certain the cable is not in contact with metal
surfaces.
The total cable length should not exceed
3 ft
[0.9 m]. A loose connection
to the spark igniter-sensor
may not conduct
a signal even though spark ignition
is
satisfactory.
Check connections
to the stud terminal
on
the S87D and the boot connection
to the spark
ig-
niter-sensor
and make certain they are clean and tight.
9
68-0014

Advertisement

Table of Contents
loading

Table of Contents