"H" Group: Motor Constants Functions

The "H" Group parameters configure the
inverter for the motor characteristics. You
must manually set H003 and H004 values to
match the motor. Parameter H006 is factory-
set. If you want to reset the parameters to the
factory default settings, use the procedure in
"Restoring Factory Default Settings" on
page
6–8. Use A044 to select the torque
control algorithm as shown in the diagram.
Func.
Name /
Code
SRW Display
H003 Motor capacity
AUX K
H203 Motor capacity, 2nd
setting
2AUXK
H004 Motor poles setting
AUX P
H204 Motor poles setting, 2nd
motor
2AUXP
H006 Motor stabilization
constant
AUX KCD
H206 Motor stabilization
constant, 2nd motor
2AUXKCD
NOTE: If you are using automatic torque boost (A041/A241 = 01) and the output
current is unstable in the low frequency range, be sure to adjust A042/A242 and
A043/A243 with H006/H206 in order to decrease the boost voltage as an addition to the
standard V/f curve.
"H" Function
Description
Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
0.4 kW
5.5 / 7.5 / 11
Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11
0.4 kW
Four selections:
2 / 4 / 6 / 8
4p
Four selections:
2 / 4 / 6 / 8
4p
Motor constant (factory set),
range is 0 to 255
100
Motor constant (factory set),
range is 0 to 255
100
L200
Inverter
2
Inverter Torque Control Algorithms
V/f control,
00
constant torque
V/f control,
01
variable torque
Run
Defaults
Mode
–FE(F)
Edit
(EU)
(USA)
Lo Hi
✘ ✘
Specified by the
capacity of each
inverter model
✘ ✘
✘ ✘
4
✘ ✘
4
✔ ✔
100
✔ ✔
100
3–63
A44
Output
–FU
Units
kW
kW
4
poles
4
poles
100
100