Honeywell TP970 Series Manual page 3

Pneumatic thermostats
Hide thumbs Also See for TP970 Series:
Table of Contents

Advertisement

BRANCHLINE
PRESSURE TAP
BLEED
EXHAUST
Fig. 2. Cross Section of TP970 and TP9600 Thermostat Showing Valve Unit and Airflow.
TP970, TP9600, TP971, TP9610, TP972, and TP9620
Thermostats are designed around a valve unit for flow
amplification rather than conventional pressure amplification.
Branchline chamber and pilot chamber design are such that
branch pressure is equal to nozzle pressure at a higher
capacity.
Figures 3, 4, and 5 are cross-sections of the valve unit only,
showing air passages and the pilot-branch diaphragm
relationship.
Figure 3 shows a valve unit in a strategic or balanced
condition. All the forces are equal; BLP equals the pilot-line
pressure.
No main air enters the branchline chamber and no exhaust
air leaves the branchline chamber. In this static condition,
the valve is sealed at both Points A and B, preventing airflow.
POINT A
BRANCH
EXHAUST
PILOT CHAMBER
Fig. 3. Valve Unit Flow Amplifier in a
Balanced (Static) Condition.
THROTTLING RANGE
ADJUSTMENT
FLAPPER
BRANCHLINE
CHAMBER
PILOT
PILOT
CHAMBER
POINT B
MAIN LINE
BRANCH
LINE
CHAMBER
VALVE
PILOT AIR
C6048-1
TP790 AND TP9600 SERIES PNEUMATIC THERMOSTATS
NOZZLE
VALVE
BRANCH LINE
Figure 4 shows the valve unit supplying air to the branch
line. This condition occurs when the bimetal sensing element
forces the Thermostat flapper toward the nozzle, decreasing
the nozzle-flapper gap and increasing the pilot pressure.
The increased pilot pressure against the pilot diaphragm
overcomes the force of the BLP on the branchline
diaphragm. This change opens the valve unit at Point B,
allowing main air to flow into the branch line. BLP builds until
the pressure against the branch diaphragm again equals the
pressure against the pilot chamber diaphragm. The main
airflow then shuts off, bringing the valve unit into a balanced
condition at a new pressure.
With direct-acting bimetal sensors, a temperature increase
closes the nozzle-flapper gap; with reverse-acting bimetal
sensors, a temperature increase opens the nozzle-flapper
gap. The arrows in the air passages in Figure 4 show the
direction of airflow.
POINT A
EXHAUST AIR
NOTE: THE SEAL AT POINT A DOES NOT
ALLOW AIR TO EXHAUST.
Fig. 4. Valve Unit Shown with Pilot
Chamber Pressure Increased.
3
CALIBRATION
SCREW
BIMETAL
SETPOINT
CAM
SETPOINT
KNOB
FILTER
RESTRICTOR
MAIN
C6047-1
LINE
POINT B
MAIN LINE
BRANCH
LINE
VALVE
PILOT AIR
C6049-1
77-9382—1