5.3

WALK / DRILL Menu Selections

Drill ON/OFF
Audible Test
5.4

I/O Menu Selections

Output ON/OFF
Enable/Disable
9000-0447 Rev. I
Is a simple ON or OFF selection. ON will activate the NACs, while
OFF will deactivate them.
Is a simple ON or OFF selection for an audible walk test. The
audible appliances will sound twice for a trouble, 3 times for a
supervisory signal and 4 times for an alarm.
Forces the toggling on or off of a specified output. These
outputs can include NAC 1, NAC 2, Municipal Circuit (if
present) and any Addressable Control Point.
Allows the user to take any addressable device on either SLC
and disconnect it through software. While disabled, a point will
report a trouble until it is enabled, but will not cause or
respond to an alarm.
Page 34 of 42