T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
4 Stage with Pump Output and Reset (continued)
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
See Fig. 27.
L1
(HOT)
L2
STAGE
4
STAGE
1
STAGE
2
STAGE
3
Device Checkout
The T775 performance can be checked out to determine if
proper operation exists.
For example, when the outside air temperature is at 50° F
(10° C), the boiler temperature should be 180° F (22° C). See
Fig. 28. Use the alternate Home screen to check that the
effective setpoint is adjusting correctly based on the outside
air temperature (Sensor B).
NOTE: The alternate Home screen does not show live
updates of the sensor temperature. It shows the tem-
perature only at the moment the button is pressed.
From the Home screen, use the button to verify
1.
the setpoint temperature for each output.
2.
Then, press the HOME button to view the actual
outside air temperature (Sensor B).
63-7147—05
SENSOR B
SENSOR A
SENSOR C
T
T
T
T775P
T
T
T
–
1
+
3
+
C
RELAY
RELAY
4
3
NC
NC
COM
C
C
NO
NO
NO
NO
NO
NO
COM
C
C
NC
NC
RELAY
RELAY
1
COM
1
T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO/FROM T775P/L AND T775S.
2
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
3
24 VAC POWER TERMINAL BLOCK.
Fig. 27. T775P wiring — 4 stage with pump output and reset.
–
1
+
3
+
C
2
120 VAC
RELAY
8
NC
COM
C
NO
NO
RELAY
2
NO
PUMP
COM
NO
BOILER DISCHARGE
SETPOINT TEMPERATURE
Fig. 28. Boiler discharge temperature vs. outside
22
T
T
T775S
120 VAC
RELAY
7
NC
C
NO
NO
NO
C
C
NC
NC
RELAY
5
6
L2
L1
(HOT)
OUTSIDE AIR
TEMPERATURE
210°
20°
200°
30°
190°
40°
180°
50°
170°
60°
160
70°
temperature.
2
M24556
M24880