Important: The times must be entered
E03
Alarm temperature difference
E04
Delay time – Alarm
E05
Compressor start-up delay
E06
Defrost type
1 = Electrical (compressor off)
2 = Hot gas (compressor on)
E07
Defrost limit temperature
E08
Defrost time limit
E09
Drainage time, evaporator
E10
Time delay, fan
E11
Evaporator fan control
1 = Fan with compressor.
2 = Continuous fan operation, except during defrosting.
3 = Fan run-on. If there is an undershoot in the cold
store temperature, the fan is switched on by
evaporator sensor T2. The fan is switched off again
once the desired cold store temperature is
attained or exceeded.
E12
Minimum permissible
cold store temp.
E13
Maximum permissible
cold store temp.
E14
Display during defrosting
1 = "dEF" in display.
2 = Current cold store temperature in display.
3 = Retaining temperature in display when defrosting
is initiated until the current cold store temperature
reaches the retained value again. This is for a maxi-
mum of 15 minutes after the end of defrosting.
Evaporator drainage time E09 and time delay fan E10 are not
respected at hot gas defrost mode E06 = 2.
The time is entered in increments
of 10 minutes in each case .
in ascending order.
14
–50 K to + 50 K
0 to 99 mins.
0 to 15 mins.
1 or 2
0 to 50 °C
1 to 99 mins.
0 to 99 mins.
0 to 500 secs.
1,2 or 3
–55 °C to E13
E12 to +50 °C
1,2 or 3
20 K
10 mins.
5 mins.
1
8 °C
25 mins.
3 mins.
30 secs.
1
–55 °C
+50 °C
1