Download Print this page

Specifications; Ordering Information - Honeywell C7650A User Manual

Solid state temperature sensor
Hide thumbs Also See for C7650A:

Advertisement

C7650A SOLID STATE TEMPERATURE SENSOR

SPECIFICATIONS

Model:
C7650A Solid State Temperature Sensor.
Case:
Duct mount.
Temperature Sensing Element:
Thermistor.
Output Signal:
10 to 20 mA current signal; increases from 10 mA to 20 mA
as temperature decreases.
Operating Ambient Temperature Range:
+40°F to +100°F (+4°C to +38°C).
Shipping Temperature Range:
-40°F to +150°F (-40°C to +66°C).
Maximum Power Consumption:
0.45 VA.
Supply Voltage:
15 to 23 Vdc.
Electrical Connections:
Two 1/4 in. (6.5 mm) quick connect terminals.
Approval:
Underwriters Laboratories Inc. Flammability Rating: UL94-5V.
Dimensions:
See Fig. 1.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1.
Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.
Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2499—1
5
(8)
16
5
3
32
(80)
3
2
4
(70)
9
16
7
(14)
32
(6)
1 (25)
Fig. 1. C7650A Thermistor Temperature Sensor
Dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
2
+
S
7
3
(96)
8
M9096

Advertisement

loading