Download Print this page

Specifications; Ordering Information - Honeywell ML6185 Manual

Spring return direct coupled actuator

Advertisement

ML6185
SPECIFICATIONS • ORDERING INFORMATION
MODELS: ML6185 Spring Return Direct Coupled Rotary
Actuators.
ML6185A: Medium Torque (50 lb-in.) Direct Coupled
Rotary Actuator without auxiliary switches and
without time-out function.
ML6185C: Medium Torque (50 lb-in.) Direct Coupled
Rotary Actuator with two line voltage rated aux-
iliary switches, without time-out function.
ML6185D: Medium Torque (50 lb-in.) Direct Coupled
Rotary Actuator without auxiliary switches and
with time-out function.
ML6185F: Medium Torque (50 lb-in.) Direct Coupled
Rotary Actuator with two line voltage auxiliary
switches and time-out function.
ELECTRICAL RATINGS:
Power Input: 24 Vac 20%, 50/60 Hz.
Power Consumption:
ML6185A-C: 12 VA maximum at 24 Vac.
ML6185D,F: 12 VA maximum at 24 Vac.
Auxiliary Switch Ratings: 120, 240 Vac: 3 AFL, 18 ALR,
1A pilot duty.
Control: Standard models include nonplenum UL/
CSA rated, 30V, 60 C, 20 gauge cable.
Auxiliary Switch: UL/CSA rated 300V 90 C, 18
gauge.
TORQUE RATINGS (at Rated Voltages):
Lift and Hold: 50 lb-in. (6 N•m).
Breakaway Minimum: 50 lb-in. (6 N•m).
Stall Minimum: 50 lb-in. (6 N•m) spring return.
When purchasing replacement and modernization products from your TRADELINE
Catalog or price sheets for complete ordering number, or specify:
1. Model number.
2. Application.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North,
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales and Service
offices in all principal cities of the world.
63-2483—2

Specifications

Stall Driving Maximum: 130 lb-in. (15 N•m).
ACTUATOR STROKE: 95 Nominal
limited.
ACTUATOR TIMING at 90 Stroke:
88 +/- 2 seconds synchronous at 60 Hz from 0 F to
140 F;
106 +/- 2 seconds at 50 Hz;
100 seconds at -30 F.
Spring Wind Timing (Upon Power Restoration Only):
100 seconds nominal at 60 Hz, 120 seconds at 50 Hz.
Spring Return Timing:
10 seconds minimum per 90 at 72 F no load;
30 seconds maximum per 90 at 72 F at rated load;
5 minutes maximum at -30 F at rated load.
AMBIENT TEMPERATURE RANGE: -30 F to +140 F
(-35 C to +60 C).
STORAGE TEMPERATURE: -30 F to 150 F (-35 C to
65 C).
HUMIDITY: 5 to 95 percent relative humidity, noncondensing.
MOUNTING: Mounts directly on horizontal 3/8 in. to
5/8 in. (12 to 16 mm) round or square damper shaft.
Minimum shaft length required: 3.5 in. (76 mm) when the
shaft attachment is made on the side of the actuator
opposite the duct; 0.65 in. (16 mm) when the hub is
mounted on the shaft before the actuator is installed. Most
actuators are shipped with specifically sized hubs. Some
models contain an assembly with assorted hub inserts.
Mounting bracket is included with most models.
DIMENSIONS: See Fig. 1.