EXHAUST
SYSTEM
REQUIREMENTS
1. CAUTION:
FOR YOUR PERSONAL
SAFETY
DO NOT
EXHAUST
DRYER INTO A CHIMNEY,
FURNACE
COLD
AIR DUCT OR ANY OTHER COMMON
DUCT, ATTIC OR
CRAWL SPACE. ACCUMULATED
LINT COULD BECOME
A FIRE HAZARD
OR MOISTURE
COULD CAUSE DAM-
AGE.
DO NOT USE 3 INCH EXHAUST
DUCT
2. You can get the parts you need for installation
from your Whirlpool
parts distributor
or your local
plumbing
and heating store.
3. We strongly
recommend
exhausting
the dryer to
the outside
to prevent
large amounts
of moisture
and lint from being blown into the room.
4. If you cannot exhaust your dryer to the outside,
use Exhaust
Deflector
Kit LCK4000
available from
your Whirlpool
Dealer.
5. Exhaust
outlet
at rear of the dryer is located as
shown in Figure 16. Detailed instructions
on spacing
for side and rear clearances can be found in the sec-
tion
"Instructions
for
Recessed or Closet
Instal-
lations."
Information
on minimum
spacing side to
side and to the rear is also found on a label located
on back panel.
/-Iz
F-J--
r-----
--3 I '
A
I
\
I
SEE
t
I
CHART
-.
ELECTRlC
]
f
'---t'
"2"
,I \
3s'
E XHA".ST
28-114"
14 19/32-
-
4"
q;
1
1%
GAS
4.3/4-
_
1
*
AZ
r
19.3/8"
-
,-,,4.'
1"
BACKVIEW
F,G",-jE
,6
SIDEVIEW
A
Non coin model
7-I/8"
Coin model
7-718"
6. We strongly
recommend
exhausting
with 4 inch
diameter
rigid
METAL
duct.
We strongly
recom-
mend METAL
flexible
duct if you use flexible
duct.
Flexible
aluminum
duct
is available
from
your
Whirlpool
dealer
or
parts
distributor.
NEVER
USE SMALLER
THAN
4 INCH EXHAUST
DUCT.
7. The
exhaust
may
be routed
up, down,
left,
right or straight through
the wall.
8. The exhaust
duct should terminate
with
an ex-
haust hood to prevent
back drafts.
The outlet
of
the
hood
must
be at least 12 inches
from
the
ground
or any
obstruction.
A louvered
exhaust
hood, Part Number
279399
is available
from your
Whirlpool
dealer or parts distributor.
An exhaust
hood with a 2% inch outlet
creates more back pres-
sure, but may be used with
shorter systems. Never
use an exhaust hood with a magnetic
latch.
9. The maximum
length of the exhaust
system de-
pends upon the type of duct used, the number
of
elbows and the type of exhausted
hood. The max-
imum
length
for both
rigid
and flexible
duct is
shown in the chart, FIG. 17.
NUMBER
Of
90 TURNS
EXHAUST
HOOD
TYPE
36 FT
26 FT
16 FT.
24 FT
16 FT.
10 FT
RIGID
METAL
METAL
DUCT
FIGURE
17
10.
Use duct
tape to seal all joints.
Never use
screws to assemble the ductwork,
screws can catch
lint.
11. Exhaust systems longer than specified will short-
en the life of the dryer and result in reduction
of
performance
such as longer
drying
time
and in-
creased use of energy.
Lint
may also accumulate
creating
a possible safety hazard. The exhaust
sys-
tem should
be cleaned
periodically,
at least every
two years.
12. We do NOT RECOMMEND
non-metallic
flex-
ible duct.
If you use non-metallic
flexible
duct you
must connect
a METAL
elbow and at least 2 feet
of METAL
duct to the dryer outlet.
The length of
the non-metallic
flexible
duct should
not exceed 7
feet, and it must be adequately
supported
to pre-
vent sagging or kinking.
See FIG. 18.
NEVER
INSTALL
ANY
TYPE
OF FLEXIBLE
DUCT CONCEALED
IN WALLS
OR CEILING
TYPICAL EXHAUST INSTALLATIONS
EXHAUST
HOODd:
I
RIGID METAL
DUCT
,,
d
I
A'1
J.,.
-'*,
!,
I
7,. :;/
1
FIGURE
18
L. ~*,b=
RECOMMENDED
IMPORTANT:
PROPER
SUPPORT IS REOUIRED+y',EXHAUST
1
FLEXIBLE
VINYL
HOOD
ALTERNATE
For your
personal
safety,
a metal elbow
and at least 2 feet of
metal
duct
must
be used at the outlet
of the dryer.
This
reduces
the possibility
of lint
blocking
the exhaust,system
and minimizes
the potential
of a fire hazard.
The 2 feet of
metal
duct
also helps make
any service
that
may be needed
easier and prevents
crushing
the flexible
duct when the dryer
is moved
to its final operating
location.
7