Honeywell Q7300H System Integration Manual page 43

Communicating subbase system integration user address manual
Hide thumbs Also See for Q7300H:

Advertisement

Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
AlarmType
The actual alarm being issued. When an alarm condition is no longer True, AlarmType is set to the sum of the
numeric value of the alarm condition and 128. The alarm type is also recorded in nvoAlarmLog.
CommFailAlrm
One or more bound network variable inputs have failed to receive an update within the specified
FAILURE_DETECT_TIME.
PgmVerAlrm
PgmVerCode of the thermostat is not compatible with this subbase software version. Further communications
with the thermostat are not allowed.
DestApplicModeErr
A bound network variable has not been received for at least the failure detect time and the default has been set
to the default value.
DestBypassErr
A bound network variable has not been received for at least the failure detect time and the default has been set
to the default value.
DestDlcShedErr
A bound network variable has not been received for at least the failure detect time and the default has been set
to the default value.
DestOccSchedErr
A bound network variable has not been received for at least the failure detect time and the default has been set
to the default value.
DestSpaceTempErr
NviSpace Temp is bound and has not been received for at least the failure detect time and the nviSpaceTemp
has been set to the default value. If there is no local space sensor, heating and cooling are turned off, but the
fan remains under normal control.
RemoteTempSenErr
Uses default occupied setpoints.
Table A4. Alarm Points (Right Continued).
43
Comments
(continued)