Cord Sets And Receptacles - Craftsman 580.675611 Operator's Manual

Ac generator 5600 watt
Hide thumbs Also See for 580.675611:
Table of Contents

Advertisement

Available languages

Available languages

CORDSETSANDRECEPTACLES
Use only high quality, well-insulated, grounded extension
cords with the generator's 120 Volt electrical receptacles.
Inspect extension cords before each use.
Checkthe ratings of all extension cords before you use them.
Extensioncord sets used should be rated for 125 Volt AC
loads at 20 Amps or greater for most electrical devices.
Some devices, however, may not require this type of
extension cord. Checkthe operator's manuals of those
devices for the manufacturer's recommendations.
,_
WARHIHG
_
verloaded electrical cords can overheat, arc, and
burn resulting in death, bodily injury,and/or
propertydamage.
* ONLYusecords ratedfor your loads.
, Followall safeties on electrical c ords.
Keepextension cords as short as possible, preferably less
than 15 feet long, to prevent voltage drop and possible
overheating of wires.
120/240 Volt AC, 30 Amp, Locking Receptacle
Use a NEMA L14-30 plug with this receptacle. Connecta
4-wire cord set rated for 250 Volt AO loads at 30 Amps (or
greater). You can usethe same 4-wire cord if you plan to
run a 120 Volt load.
4-WireCordSet
J
120 Volt AC, 20 Amp, Duplex Receptacles
Eachduplex receptacle is protected against overload by a
double pole rocker switch circuit breaker.
Use each receptacleto operate 120 Volt AO,single-phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at
20 Amps of current. Use cord sets that are rated for 125 Volt
AC loads at 20 Amps (or greater). Inspect cord sets before
each use.
GEHERATOR ADAPTERCORDSET
The generator comes with a 25' generator adapter cord set
designedto provide two sets of 120 Volt, 20 Amp outlets
from one 120 Volt, 20 Amp duplex receptacle.
(Neutral)
Y (Hot)
|
X (Hot)
NEMA L14-30
/--7I-7 Ground(Green)
This receptaclepowers 120/240 Volt A6, 60 Hz, single phase
loads requiring up to 5,600 watts of power (5.6 kW) at
23.3 Amps for 240 Volts or two independent 120 Volt loads
at 23.3 Amps each. The outlet is protected by a double pole
rocker switch circuit breaker.
NOTICE
Receptaclesmay be marked with rating value greater than
_ienerator out_
NEVER attemptto powera devicerequiringmoreamperage
than generator o r receptacle cansupply.
DONOT overloadthe generator. S eeDon't Overload Generator.
The maximum load on each outlet is 20 Amps. The maximum
total load on both black wire outlets or white stripe wire outlets
is 20 Amps. If an extension cord is used with adaptercord set,
be sure extensioncord is rated for 125V at 20 Amps.
NOTE:Follow all safety precautions when connecting any
extension cord or device to the generator.
12