Design And Construction; Inverted Construction And Primary Circuit; Secondary Circuit; Paper-Oil Insulation - GE OSKF Instruction Manual

Current transformer
Table of Contents

Advertisement

Instruction Manual

2. DESIGN AND CONSTRUCTION

2.1. Inverted construction and
primary circuit
The active part of the OSKF current
transformer
is
porcelain insulator. The advantages of
this construction concern the primary
circuit conception. The primary circuit is
short, rigid and straight, minimizing
heating.
In
electrodynamics forces more easily,
allowing high level performance, relating
to electrodynamics and thermal effects,
in a presence of short-circuit currents.
The primary bar (simple or multiple
ratios)
with
centered
to
magnetic flow in uniform way to avoid
local
saturation.
allows also better accuracy in transient
conditions.

2.2. Secondary circuit

The ring-shaped magnetic circuits are
manufactured either from very high
permeability grain oriented steel or from
nickel alloy. In order to achieve a
satisfactory
protection cores can also be provided
with gaps.
OSKF may have metering and protection
cores with different loads and different
accuracy classes. Secondary turns are
evenly wound around the circumference
of the ring-shaped cores. Changing ratio
is available by means of taps on the
secondary or primary side.
© GE Grid Solutions
located
above
addition,
it
bears
magnetic
circuits
assure
a
distributed
This
arrangement
transient
behavior,
All secondary windings are enclosed in
an aluminum box which protects them
against high frequency disturbances
while acting as a low voltage shielding
electrode.
extended up to the base by an aluminum
the
tube which contains all secondary leads.
The
connections is designed to support
defect currents.
The bottom of the hermetic and
watertight secondary terminal box is
closed by a fitted plate, with or without
cable gland depending on customer
requirements.
are

2.3. Paper-oil insulation

Insulation
secondary circuits is made by multiple
layers of insulating papers impregnated
with mineral oil.
To protect the oil from the environment,
the CT head is closed by a metallic
bellows.
construction, the bellows adapts to the
changes in oil volume without producing
any increase or decrease in internal
pressure. This bellows resists aging and
corrosion.
This
aluminum
cross
section
of
between
primary
Due
to
its
wave
box
is
the
earth
and
shape
6

Advertisement

Table of Contents
loading

Table of Contents