Summary of Contents for Honeywell VERSAFLOW MAG 200

  • Page 1 VERSAFLOW MAG 2000 VERSAFLOW MAG 2000 VERSAFLOW MAG 2000 VERSAFLOW MAG 2000 Quick Start Quick Start Quick Start Quick Start Electromagnetic flowmeter in sandwich version The documentation is only complete when used in combination with the relevant documentation for the signal converter.
  • Page 2: Table Of Contents

    CONTENTS VERSAFLOW MAG 2000 1 Safety instructions 2 Installation 2.1 Scope of delivery....................... 6 2.2 Device description ......................7 2.3 Nameplates (examples) ....................8 2.4 Storage ..........................9 2.5 Transport .......................... 9 2.6 Pre-installation requirements ..................9 2.7 General requirements ....................10 2.7.1 Vibration ..........................
  • Page 3 CONTENTS VERSAFLOW MAG 2000 34-VF-25-64 iss.3 GLO April 18 US www.honeywellprocess.com...
  • Page 4: Safety Instructions

    SAFETY INSTRUCTIONS VERSAFLOW MAG 2000 Warnings and symbols used DANGER! This information refers to the immediate danger when working with electricity. DANGER! These warnings must be observed without fail. Even partial disregard of this warning can lead to serious health problems and even death. There is also the risk of seriously damaging the device or parts of the operator's plant.
  • Page 5 SAFETY INSTRUCTIONS VERSAFLOW MAG 2000 34-VF-25-64 iss.3 GLO April 18 US www.honeywellprocess.com...
  • Page 6: Installation

    INSTALLATION VERSAFLOW MAG 2000 2.1 Scope of delivery INFORMATION! Do a check of the packing list to make sure that you have all the elements given in the order. INFORMATION! Inspect the packaging carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer.
  • Page 7: Device Description

    INSTALLATION VERSAFLOW MAG 2000 2.2 Device description Electromagnetic flowmeters are designed exclusively to measure the flow and conductivity of electrically conductive, liquid media. Your measuring device is supplied ready for operation. The factory settings for the operating data have been made in accordance with your order specifications. The following versions are available: •...
  • Page 8: Nameplates (Examples)

    INSTALLATION VERSAFLOW MAG 2000 2.3 Nameplates (examples) INFORMATION! Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate. 1 Manufacturer name, logo and address 2 CE sign with number(s) of notified body / bodies 3 Type designationof the flowmeter and manufacturer date 4 Calibration data...
  • Page 9: Storage

    INSTALLATION VERSAFLOW MAG 2000 2.4 Storage • Store the device in a dry and dust-free location. • Avoid lasting direct exposure to the sun. • Store the device in its original packaging. • Storage temperature: -50...+70°C / -58...+158°F 2.5 Transport Signal converter •...
  • Page 10: General Requirements

    INSTALLATION VERSAFLOW MAG 2000 2.7 General requirements INFORMATION! The following precautions must be taken to ensure reliable installation. Make sure that there is adequate space to the sides. • • Protect the signal converter from direct sunlight and install a sun shade if necessary. •...
  • Page 11: Installation Conditions

    INSTALLATION VERSAFLOW MAG 2000 2.8 Installation conditions 2.8.1 Inlet and outlet Use straight inlet and outlet pipe sections to prevent flow distortion or swirl, caused by bends and T-sections. Figure 2-6: Recommended inlet and outlet section 1 Refer to chapter "Bends in 2 or 3 dimensions" 2 DN 2.8.2 Bends in 2 or 3 dimensions Figure 2-7: Inlet when using 2 and/or 3 dimensional bends upstream of the flowmeter...
  • Page 12: T-Section

    INSTALLATION VERSAFLOW MAG 2000 2.8.3 T-section Figure 2-8: Distance behind a T-section 10 DN 2.8.4 Bends CAUTION! Avoid draining or partial filling of the flow sensor www.honeywellprocess.com 34-VF-25-64 iss.3 GLO April 18 US...
  • Page 13: Open Discharge

    INSTALLATION VERSAFLOW MAG 2000 2.8.5 Open discharge Figure 2-9: Installation in front of an open discharge 2.8.6 Flange deviation CAUTION! Max. permissible deviation of pipe flange faces: 0.5 mm / 0.02" Figure 2-10: Flange deviation 2.8.7 Pump Figure 2-11: Installation behind a pump 34-VF-25-64 iss.3 GLO April 18 US www.honeywellprocess.com...
  • Page 14: Control Valve

    INSTALLATION VERSAFLOW MAG 2000 2.8.8 Control valve Figure 2-12: Installation in front of a control valve 2.8.9 Air venting and vacuum forces Figure 2-13: Air venting 2 Air ventilation point Figure 2-14: Vacuum www.honeywellprocess.com 34-VF-25-64 iss.3 GLO April 18 US...
  • Page 15: Mounting Position

    INSTALLATION VERSAFLOW MAG 2000 2.8.10 Mounting position Figure 2-15: Mounting position 34-VF-25-64 iss.3 GLO April 18 US www.honeywellprocess.com...
  • Page 16: Mounting

    INSTALLATION VERSAFLOW MAG 2000 2.9 Mounting 2.9.1 Torques and pressure WARNING! Please use stainless steel A2 / 6.9 class bolts. • Make sure the connecting flanges are of type raised face (RF). • Figure 2-16: Tighten the bolts in fixed order, see picture. Max.
  • Page 17 INSTALLATION VERSAFLOW MAG 2000 INFORMATION! The specified torque values are dependent on variables (temperature, bolt material, gasket material, lubricants, etc.) which are not within the control of the manufacturer. Therefore the values should be regarded as indicative only. EN 1092-1 Nominal Counter flanges &...
  • Page 18: Electrical Connections

    ELECTRICAL CONNECTIONS VERSAFLOW MAG 2000 3.1 Safety instructions DANGER! All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate! DANGER! Observe the national regulations for electrical installations! DANGER! For devices used in hazardous areas, additional safety notes apply;...
  • Page 19: Virtual Reference For Twm 9000 (C, W And F Version)

    ELECTRICAL CONNECTIONS VERSAFLOW MAG 2000 Grounding rings Figure 3-2: Grounding ring number 1 Grounding ring number 1 (optional for DN25...150 / 1...6"): Grounding ring number 1 (optional for DN25...150 / 1...6"): Thickness: 3 mm / 0.1" (tantalum: 0.5 Grounding ring number 1 (optional for DN25...150 / 1...6"): Grounding ring number 1 (optional for DN25...150 / 1...6"): mm / 0.02") 3.3 Virtual reference for TWM 9000 (C, W and F version)
  • Page 20: Technical Data

    TECHNICAL DATA VERSAFLOW MAG 2000 4.1 Dimensions and weights Remote version: Remote version: Remote version: Remote version: a = 88 mm / 3.5" DN2.5...15 / 1/10...1/2" b = 139 mm / 5.5" c = 106 mm / 4.2" Total height = H + a Remote version: Remote version: Remote version:...
  • Page 21 TECHNICAL DATA VERSAFLOW MAG 2000 Figure 4-1: Construction details DN2.5...15 / 1/10...1/2" 1 O-ring 2 Grounding ring Figure 4-2: Construction details DN25...100 / 1...4" 1 Situation without grounding rings 2 Gasket INFORMATION! All data given in the following tables are based on standard versions of the flow sensor only. •...
  • Page 22 TECHNICAL DATA VERSAFLOW MAG 2000 Nominal Dimensions [mm] Approx. size weight [kg] Ød1 Ød4 1 Total fitting length of flowmeter with integrated rings: dimension L + 2 x gasket thickness. 2 Total fitting length of flowmeter without rings: dimension L only. Nominal Dimensions [inches] Approx.
  • Page 23: Technical Data

    TECHNICAL DATA VERSAFLOW MAG 2000 34-VF-25-64 iss.3 GLO April 18 US www.honeywellprocess.com...
  • Page 24 Houston, TX 77042 Houston, TX 77042 www.honeywellprocess.com www.honeywellprocess.com www.honeywellprocess.com www.honeywellprocess.com © Honeywell International Inc. © Honeywell International Inc. © Honeywell International Inc. © Honeywell International Inc. Subject to change without notice. Subject to change without notice. Subject to change without notice.