The bottom left portion contains the logic, or operator, quantifier that 
determines how conditions are calculated.  Options available in this 
field are: 
  
Operator 
Symbol 
No operator 
---
Equal to 
=
Equal to or smaller than 
<=
Smaller than 
<
Equal to or larger than 
>=
Larger than 
>
Not equal to 
!=
When the maximum value is reached, an action is 
max 
triggered.  It  will not be deactivated until levels fall 
below minimum value 
When concentrations fall below minimum value, an 
min 
action is triggered. It will not be deactivated until 
concentrations rise above set maximum value 
The time since calibration reported by the sensor is 
evaluated. This number is also listed in the "1. TxInfo / 
Operating Times / Since Calib" menu. Further dialog 
TSC 
allows the time limit to be set from 0 minutes to 98 
months. This logic function is supported only with 
E³Point transmitters.
 
 
 