Option Setting Error Of Outdoor Unit - Samsung AM080 XV Series Service Manual

Hide thumbs Also See for AM080 XV Series:
Table of Contents

Advertisement

Troubleshooting

4-3-55 Option setting error of outdoor unit

Outdoor unit display
Indoorunit display
• Refer to the judgment method below.
Judgment Method
• Option setting error of outdoor unit
Special Cause
(There is No Compressor start in a Unit because of Compressor Cut off Option Setting. )
1. Cause of problem
Is the Compressor breakdown
setting value is "not set"?
Is the outdoor unit EEPROM accurately
connected to connector?
Download relevant model EEPROM and then reset.
※ Execute automatic commissioning for UP
cancellation after EEPROM download.
4-82
(Operation) ×(Reservation)
Yes
Yes
(Blast) ×(Filter) ×(Defrost)
Set the compressor breakdown setting
value as "not set"
No
※ When There is No Compressor start in a Unit
because of Compressor Cut off Option
Setting, E560.
No
Connect outdoor unit EEPROM and then reset.