7.2 HARDWARE FUNCTIONAL TESTING
The digital inputs and trip coil supervision can be verified easily with a simple switch or pushbutton. Verify the
SWITCH +24 V DC with a voltmeter. Perform the steps below to verify functionality of the digital inputs.
1. Open switches of all of the digital inputs and the trip coil supervision circuit.
2. View the status of the digital inputs and trip coil supervision in:
A1 STATUS\DIGITAL INPUTS
3. Close switches of all of the digital inputs and the trip coil supervision circuit.
4. View the status of the digital inputs and trip coil supervision in:
A1 STATUS\DIGITAL INPUTS
Table 7–10: DIGITAL INPUTS
INPUT
ACCESS
TEST
STARTER STATUS
EMERGENCY RESTART
REMOTE RESET
ASSIGNABLE INPUT 1
ASSIGNABLE INPUT 2
ASSIGNABLE INPUT 3
ASSIGNABLE INPUT 4
TRIP COIL SUPERVISION
7
The 469 specification for analog input and analog output accuracy is ±1% of full scale. Perform the steps below
to verify accuracy. Verify the Analog Input +24 V DC with a voltmeter.
a) 4-20 mA
1. Alter the following setpoints:
S12 ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1: 4-20 mA
S12 ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1 MINIMUM: 0
S12 ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1 MAXIMUM: 1000 (repeat for analog inputs 2 to 4)
2. Analog output values should be ±0.2 mA on the ammeter. Measured analog input values should be ±10
units. Force the analog outputs using the following setpoints:
S13 TESTING\TEST ANALOG OUTPUT\FORCE ANALOG OUTPUTS FUNCTION: Enabled
S13 TESTING\TEST ANALOG OUTPUT\ANALOG OUTPUT 1 FORCED VALUE: 0%
(enter desired percent, repeat for analog outputs 2 to 4)
7-6

7.2.6 DIGITAL INPUTS AND TRIP COIL SUPERVISION

EXPECTED STATUS
PASS /
(SWITCH OPEN)
FAIL
Open
Open
Open
Open
Open
Open
Open
Open
Open
No Coil
469 Motor Management Relay
EXPECTED STATUS
(SWITCH CLOSED)
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Shorted
Coil

7.2.7 ANALOG INPUTS AND OUTPUTS

GE Power Management
7 TESTING
PASS /
FAIL