Zennio inBOX 24 vT Manual

Zennio inBOX 24 vT Manual

Multifunction actuator for flush mounting

Advertisement

Quick Links

inBOX 24 vT / inBOX 20 vT
Multifunction Actuator for Flush Mounting
ZIOIB24VT
ZIOIB20VT
dsñkmfroi
Application program version: [1.2], [1.4]
User manual edition: [1.4]_b
www.zennio.com

Advertisement

Table of Contents
loading

Summary of Contents for Zennio inBOX 24 vT

  • Page 1 ➢ inBOX 24 vT / inBOX 20 vT Multifunction Actuator for Flush Mounting ZIOIB24VT ZIOIB20VT dsñkmfroi Application program version: [1.2], [1.4] User manual edition: [1.4]_b www.zennio.com...
  • Page 2: Table Of Contents

    24 vT / inBOX 20 vT CONTENTS Contents ............................2 Document Updates ........................3 Introduction .......................... 4 1.1 inBOX 24 vT / inBOX 20 vT ....................4 1.2 Installation ........................5 1.3 Start-Up and Power Loss ....................6 Configuration......................... 7 2.1 General ..........................7 2.2 Inputs (Only inBOX 24 vT) ....................
  • Page 3: Document Updates

    24 vT / inBOX 20 vT DOCUMENT UPDATES Version Changes Page(s) Erratum correction on functionalities listed for inBOX 24 vT. 4, 8 [1.4]_b Separation of communication objects table in two tables. 21, 24 https://www.zennio.com Technical Support: https://support.zennio.com...
  • Page 4: Introduction

    1 INTRODUCTION 1.1 inBOX 24 vT / inBOX 20 vT inBOX 24 vT and inBOX 20 vT from Zennio are two versatile KNX actuators featuring two relay outputs (together with four analogue-digital inputs, in the case of inBOX 24 vT) and a variety of functions. Their particularly small size makes them suitable for installation within mechanism boxes, junction boxes, roller shutter boxes or any other location where the available space is limited.
  • Page 5: Installation

    KNX connector. Figure 1. inBOX 24 vT. Elements Note: the above element diagram refers to inBOX 24 vT. It is entirely analogous for inBOX 20 vT, although the inputs are not available. The main elements of the device are described next.
  • Page 6: Start-Up And Power Loss

    To get detailed information about the technical features of this device, as well as on the installation and security procedures, please refer to the corresponding Datasheet, bundled with the original package of the device and also available at www.zennio.com. 1.3 START-UP AND POWER LOSS During the start-up of the device, the Test/Prog.
  • Page 7: Configuration

    Figure 2. Default screen Once activated, Inputs (only on inBOX 24 vT), Outputs, Logic Functions, Thermostats (only on inBOX 24 vT), Master Light (only on inBOX 24 vT), Scene Temporisation and Manual Control bring additional tabs to the menu on the left. These functions and their parameters will be explained in later sections of this document.
  • Page 8 24 vT / inBOX 20 vT Sending of Indication Objects (0 and 1) on Bus Voltage Recovery: this parameter lets the integrator activate two new communication objects (“Reset 0” and “Reset 1”), which will be sent to the KNX bus with values “0” and “1”...
  • Page 9: Inputs (Only Inbox 24 Vt)

    ETS). Motion Detector, for the connection of a motion detector from Zennio. 2.2.1 BINARY INPUT Please refer to the specific user manual “Binary Inputs”, available in the inBOX 24 vT ¡product section, at the Zennio website (www.zennio.com). 2.2.2 TEMPERATURE PROBE Please refer to the specific user manual “Temperature Probe”, available in the inBOX...
  • Page 10: Outputs

    For detailed information about the functionality and the configuration of the related parameters, please refer to the following specific manuals, all of them available in the inBOX 24 / 20 vT product section at the Zennio homepage (www.zennio.com): Individual outputs.
  • Page 11 24 vT / inBOX 20 vT mode. After that, an additional press will turn the LED yellow and then off, once the button is released. This way, the device leaves the Test On mode. Note that it will also leave this mode if a bus power failure takes place.
  • Page 12 24 vT / inBOX 20 vT Test On Mode After entering the Test On mode, it will only be possible to control the outputs through the on-board pushbuttons. Orders received through communication objects will be ignored, with independence of the channel or the output they are addressed to.
  • Page 13 24 vT / inBOX 20 vT Figure 5. Manual control screen Manual Control: options are “Disabled”, “Only Test Mode Off”, “Only Test Mode On” and “Test Mode Off + Test On Mode” (default). Depending on the selection, the device will permit using the manual control under the Test Off, the Test On, or both modes.
  • Page 14: Logic Functions

    Please refer to the specific “Logic Functions” user manual (available in the inBOX 24 / 20 vT product section at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
  • Page 15: Thermostats (Only Inbox 24 Vt)

    24 vT / inBOX 20 vT 2.5 THERMOSTATS (ONLY inBOX 24 vT) inBOX 24 vT implements one Zennio thermostat which can be enabled and configured independently. Please refer to the specific “Zennio Thermostat” user manual (available in the inBOX 24 vT product section at the Zennio homepage, www.zennio.com) for detailed...
  • Page 16: Master Light (Only Inbox 24 Vt)

    24 vT / inBOX 20 vT 2.6 MASTER LIGHT (ONLY inBOX 24 vT) The Master Light function brings the option to monitor the state of up to 12 light sources –or any other functionally-similar element whose state is transmitted through a binary object–...
  • Page 17 24 vT / inBOX 20 vT Trigger Value: sets the value (“0”, “1” or “0/1”, being the latter the default option) that will trigger, when received through “[ML] Trigger”, the master action (the general switch-off or the courtesy switch-on).
  • Page 18 24 vT / inBOX 20 vT (when the courtesy switch-on takes place), in contrast to object “[ML] General Switch-Off: Binary Object”, which sends the value “0” (during the general switch-off, as explained above). Figure 6. Sending of Indication objects on bus voltage recovery https://www.zennio.com...
  • Page 19: Scene Temporisation

    24 vT / inBOX 20 vT 2.7 SCENE TEMPORISATION The scene temporisation allows imposing delays over the scenes of the outputs. These delays are defined in parameters, and can be applied to the execution of one or more scenes that may have been configured.
  • Page 20 24 vT / inBOX 20 vT Figure 8. Configuration of the scene temporisation Therefore, parameter “Scene m. Z Delay” defines the delay that will be applied to the action defined in Z for the execution of scene m (where Z may be a specific individual output, shutter channel or fan coil module).
  • Page 21: Annex I. Communication Objects Inbox 20 Vt

    24 vT / inBOX 20 vT ANNEX I. COMMUNICATION OBJECTS INBOX 20 VT “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
  • Page 22 24 vT / inBOX 20 vT 1 Bit C - W - - DPT_Trigger [CA] Stop 0 = Stop; 1 = Stop 0, 1 = Up, Down or Stop, 1 Bit C - W - - DPT_Trigger [CA] Switched Control...
  • Page 23 24 vT / inBOX 20 vT Position 57, 58, 59, 60, 61, 62, 63, 64, 65, 66, 67, 68, 69, 70, 71, 72, 73, 74, 75, 76, 77, 78, 79, 80, 81, 82, 83, 84, 85, 86, 87, 88,...
  • Page 24: Annex Ii. Communication Objects Inbox 24 Vt

    24 vT / inBOX 20 vT ANNEX II. COMMUNICATION OBJECTS INBOX 24 VT “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
  • Page 25 24 vT / inBOX 20 vT 2 Bytes C - W - - DPT_Value_Temp -273.00º - 670433.28º [Tx] Setpoint Thermostat Setpoint Input 2 Bytes C - W - - DPT_Value_Temp -273.00º - 670433.28º [Tx] Basic Setpoint Reference Setpoint 0 = Decrease Setpoint; 1 =...
  • Page 26 24 vT / inBOX 20 vT 1 Bit C R - T - DPT_Switch [ML] General Status Binary Status [ML] General Switch Off: Binary 1 Bit C - - T - DPT_Switch Switch Off Sending Object 1 Byte C - - T -...
  • Page 27 24 vT / inBOX 20 vT 0x1 (Dec. by 100%) 0x7 (Dec. by 1%) 0x8 (Stop) 0xD (Inc. by 100%) 0xF (Inc. by 1%) 0x0 (Stop) 0x1 (Dec. by 100%) 0x7 (Dec. by 1%) 4 Bit C - - T -...
  • Page 28 24 vT / inBOX 20 vT 1 Bit C - - T - DPT_Switch [Ix] [Long Press] 1 Sending of 1 1 Bit C - W T - DPT_Switch [Ix] [Long Press] 0/1 Switching Switching 0/1 1 Bit C - - T -...
  • Page 29 24 vT / inBOX 20 vT [Ix] [Switch/Sensor] Alarm: 1 Bit C R - T - DPT_Alarm 1 = Alarm; 0 = No Alarm Breakdown or Sabotage [Ix] [Long Press] Constant Value 2 Bytes C - - T - 9.xxx...
  • Page 30 24 vT / inBOX 20 vT 0 = Nothing; 1 = Motion detected 121, 150, 179, 208 1 Bit C - W - - DPT_Start [Ix] External Motion Detection by an external sensor 122, 127, 132, 151, 156, 161,...
  • Page 31 24 vT / inBOX 20 vT Depending on the Last Move 1 Bit C - W - - DPT_Enable [CA] Lock 0 = Unlock; 1 = Lock 1 Byte C - W - - DPT_Scaling 0% - 100% [CA] Shutter Positioning 0% = Top;...
  • Page 32 24 vT / inBOX 20 vT 282, 283, 284, 285, 286, 287, 288, 289, 290, 291, 292, 293, 294, 295, 296, 297, 298, 299, 300, 301, 302, 303, 304, 305, 306, 307 308, 309, 310, 311, 312, 313, 314, 315, 316, 317, 318, 319,...
  • Page 33 Join and send us your inquiries about Zennio devices: https://support.zennio.com Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002. www.zennio.com info@zennio.com...