Mitsubishi Electric CITY MULTI CMB-P-NU-G Installation Manual
Mitsubishi Electric CITY MULTI CMB-P-NU-G Installation Manual

Mitsubishi Electric CITY MULTI CMB-P-NU-G Installation Manual

Air-conditioners for building application indoor unit

Advertisement

Available languages

Available languages

Quick Links

Air-Conditioners For Building Application
INDOOR UNIT
CMB-P-NU-G
CMB-P-NU-GA (MAIN BC CONTROLLER)
CMB-P-NU-GB (SUB
CMB-P-NU-HA (MAIN BC CONTROLLER)
CMB-P-NU-HB (SUB
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
BC CONTROLLER)
BC CONTROLLER)

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric CITY MULTI CMB-P-NU-G

  • Page 1 Air-Conditioners For Building Application INDOOR UNIT CMB-P-NU-G CMB-P-NU-GA (MAIN BC CONTROLLER) CMB-P-NU-GB (SUB BC CONTROLLER) CMB-P-NU-HA (MAIN BC CONTROLLER) CMB-P-NU-HB (SUB BC CONTROLLER) INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. MANUEL D’INSTALLATION Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
  • Page 4: Checking The Installation Site

    1. For hanging from the ceiling 2.4. Checking the installation site [Fig. 2.2.1] Check that the difference of elevation between indoor and outdoor units and the length of refrigerant piping are within the following limitations. 1. CMB-P104, 105, 106, 108, 1010, 1013, 1016G (In the case the outdoor unit is 12.5-hp (P120 model) or less, and 16 or fewer ports are used.) [Fig.
  • Page 5 Distance between BC controller and farthest indoor unit (Unit: m [ft]) Item Piping portion Allowable value 70 [229] Not to exceed the F+G+A+B+C maximum refriger- Total piping length +D+E+a+b 60 [196] ant piping length *1 +c+d+e+f 50 [164] 165 [541] or less (Equivalent length of Longest piping length F(G)+A+C+E+f...
  • Page 6 [Fig. 2.4.3] ●Restrictions on piping length PURY-P72/96THMU-A, PURY-P72/96YHMU-A PURY-P216/240TSHMU-A, PURY-P216/240YSHMU-A PURY-P72/96TJMU-A, PURY-P72/96YJMU-A PURY-P216/240TSJMU-A, PURY-P216/240YSJMU-A 1000 [3280] 1000 [3280] 900 [2952] 900 [2952] 800 [2624] 800 [2624] 700 [2296] 700 [2296] 600 [1968] 600 [1968] 500 [1640] 500 [1640] 400 [1312] 400 [1312] 300 [984] 300 [984]...
  • Page 8: Refrigerant Piping Work

    1. Size of BC controller’s end connection piping [Fig. 4.1.1] BC CONTROLLER/MAIN BC CONTROLLER SUB BC CONTROLLER High pressure Low pressure Total capacity High pressure Low pressure Unit model Model name Model name Liquid side (mm [in]) side (mm [in]) side (mm [in]) of indoor units (gas) side (mm [in])
  • Page 9: Insulating Refrigerant Pipes

    As shown in 3, install a collecting pipe about 100 mm [3-15/16 in] below the 4.3. Insulating refrigerant pipes • drain ports and give it a downward pitch of more than 1/100. This collecting Be sure to wind heat-resisting polyethylene form of more than 20 mm [13/16 in] in pipe should be of VP-30.
  • Page 10: Setting Addresses And Operating Units

    6. Setting addresses and operating units s When connecting multiple indoor units to one branch port The address switch of each BC controller is set to “000” when shipped from the factory. • Indoor units connected to one branch port can only be operated in the same •...
  • Page 13: Lieu D'installation

    2. Sélection d’un lieu d’installation 2.1. À propos du produit 2.3. Espace requis pour l’installation et pour l’entretien • Cet appareil utilise un frigorigène de type R410A. • La tuyauterie des systèmes utilisant le R410A peut être différente de celle des 1.
  • Page 14 2.4. Vérification du lieu d’installation Distance entre le contrôleur BC et l’appareil intérieur le plus éloigné Vérifier que la différence d’élévation entre les appareils intérieurs et extérieurs et la 70 [229] longueur des tuyaux de réfrigérant soient conformes aux spécifications requises. 60 [196] 1.
  • Page 15 Distance entre le contrôleur BC principal et l’appareil intérieur le plus éloigné (Unité : m [ft]) Portion de Élément Valeur autorisée 70 [229] tuyauterie F+G+A+B+C Ne dépassez pas la 60 [196] Longueur de tuyauterie totale +D+E+a+b longueur de tuyau de +c+d+e+f frigorigène maximum *1 50 [164]...
  • Page 16 [Fig. 2.4.3] ●Restrictions de longueur de la tuyauterie PURY-P72/96THMU-A, PURY-P72/96YHMU-A PURY-P216/240TSHMU-A, PURY-P216/240YSHMU-A PURY-P72/96TJMU-A, PURY-P72/96YJMU-A PURY-P216/240TSJMU-A, PURY-P216/240YSJMU-A 1000 [3280] 1000 [3280] 900 [2952] 900 [2952] 800 [2624] 800 [2624] 700 [2296] 700 [2296] 600 [1968] 600 [1968] 500 [1640] 500 [1640] 400 [1312] 400 [1312] 300 [984]...
  • Page 18 1. Dimension des embouts d’assemblage du contrôleur BC [Fig. 4.1.1] CONTRÔLEUR BC/CONTRÔLEUR BC PRINCIPAL CONTRÔLEUR BC SECONDAIRE Côté haute Côté basse Capacité totale des Côté haute pression Côté basse pression Côté liquide Modèle de l’appareil Nom du modèle Nom du modèle pression (mm[in]) pression (mm [in]) appareils intérieurs...
  • Page 19: Mise En Place Du Tuyau D'écoulement

    [Fig. 4.2.1] 250 [9-27/32] 1500-2000 [59-1/16-78-3/4] A Pente vers le bas de plus de 1/100 B Matière isolante C Equerre de support D Port d’évacuation de l’écoulement E Tuyau d’écoulement (200 [7-7/8] de long, fournie) A Couper ici. B Déposer le capuchon brasé F Ruban de fixation (fourni) G Attache pour tuyau (fournie) 4.3.
  • Page 24 This product is designed and intended for use in the residential, commer- cial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN WT05857X01...