Appendix A
PW-6000 Web Server and Pro-Watch Channels
The PW-6000 web server's host port configuration requires corresponding changes in
the way the Pro-Watch's channels are configured. The PW-6000 web server host
ports and the Pro-Watch channel ports must have the correct values to communicate
with each other.
Follow these steps:
1. Set the PW-6000 hardware configuration:
2. Set the host port configuration of the PW-6000 web server:
PW-6000 Installation and Configuration Guide, Document 800-00005, Revision A
a. On the controller board, set the jumpers J8, J9, J10 on Port1 to
RS-485.
b. On Port1, connect the pins as follows:
– pin1 = TR+
– pin2 = TR-
– pin5 = GND to RS-485 terminals of the Intelligent "Auto"
Converter PW5K1CVT1 (i.e., PW-5000 RS-232/RS-485
converter)
c. Connect the RS-232 terminal of the PW5K1CVT1 converter to the
serial port of your Pro-Watch application server.
a. Login to the Access Control Device Server Configuration Manager.
b. Set the Primary Host fields as follows:
– Connection Type = IP Server
– Port Number = 3001
– Data Security = Allow All
c. Set the Alternate Host Port fields as follows:
– Connection Type = Serial-RS-485
– Baud Rate= 38400
– Data Security = None
– Flow Control = RTS Toggle
Get other manuals https://www.bkmanuals.com