Lenovo RT5.0kVA Installation And User Manual page 23

3u rack or tower ups
Table of Contents

Advertisement

In/Out settings
Submenu
Output voltage
Output frequency
Output mode
Input volt hysteresis
High Efficiency mode
Bypass transfer
Interrupt time
Overload prealarm
Redundancy mode
Available settings
Enable or disable the
buzzer if an alarm occurs.
[200V] [208V] [220V] [230V]
[240V]
Can be changed only in
Standby mode
Frequency converter:
[Enabled] [Disabled]
Frequency settable in
frequency converter mode
[Industrial] [Network]
Set UPS behavior regarding
transfer on Bypass
Sets input voltage
hysteresis from 1 to 10V
[Enabled] [Disabled]
Power the output from
Bypass for high efficiency
[Transfer if BP AC NOK]
[Enabled] [Disabled]
Allow transfer on Bypass
out of tolerance
If Bypass transfer is
enabled, Interrupt time:
[10ms] [20ms]
Define break duration when
transfer on Bypass
[10%] ... [102%]
Load % when overload
alarm occurs
[Unitary UPS] [Hot Standby]
Force slew rate value to
0.5Hz/s
Default settings
[208V]
[Disabled]
[Network]
[10V]
[Disabled]
[Disabled]
[10ms]
[102%]
[Unitary UPS]
11
.