Hitachi RPC-1.5FSR Technical Catalogue

Inverter-driven split system heat pump air conditioners set free fsr indoor units, indoor units, ceiling type
Table of Contents

Advertisement

TECHNICAL CATALOG
HITACHI INVERTER-DRIVEN SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
- SET FREE FSR INDOOR UNITS -
Technical Catalog
Models
< Indoor Units >
● Ceiling Type
RPC-1.5FSR
RPC-2.5FSR
RPC-4.0FSR
RPC-6.0FSR
RPC-2.0FSR
RPC-3.0FSR
RPC-5.0FSR
TCI-20007

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi RPC-1.5FSR

  • Page 1 TECHNICAL CATALOG HITACHI INVERTER-DRIVEN SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS - SET FREE FSR INDOOR UNITS - Technical Catalog Models < Indoor Units > ● Ceiling Type RPC-1.5FSR RPC-2.0FSR RPC-2.5FSR RPC-3.0FSR RPC-4.0FSR RPC-5.0FSR RPC-6.0FSR TCI-20007...
  • Page 3 IMPORTANT NOTICE ● HITACHI pursues a policy of continuing improvement in design and performance of products. The right is therefore reserved to vary specifications without notice. ● HITACHI cannot anticipate every possible circumstance that might involve a potential hazard. ● This heat pump air conditioner is designed for standard air conditioning only. Do not use this heat pump air conditioner for other purposes such as drying clothes, refrigerating foods or for any other cooling or heating process. ● Do not install the unit at the following places. It may cause a fire, deformation, corrosion or failure. * Places where oil (including machinery oil) may be present in quantities. * Places where a lot of sulfide gas drifts, such as hot springs. * Places where inflammable gas may be generated or flow. * Places where strong salty wind blows, such as coast regions. * Places with an atmosphere of acidity or alkalinity. ● Do not install the unit in the place where silicon gas drifts. If the silicon gas attaches to the surface of the heat exchanger, the fin surface repels water. As a result, drain water splashes outside of the drain pan and splashed water runs inside of the electrical box. In the end, water leakage or electrical devices’ failure may occur. ● Pay attention to the following points when installing the unit in a hospital or other facilities where electromagnetic waves are generated from medical equipment. * Do not install the unit in the place where electromagnetic waves are directly radiated to the electrical box, controller cable or wired controller. * Install the unit at least 3 meters away from devices generating electromagnetic waves, such as a radio. ● Do not install the unit in the place where animals and plants catch the direct outlet air. It could adversely affect animals and plants. ● The installer and system specialist shall secure safety against the refrigerant leakage according to the local regulations or standards. The following standards may be applicable, if the local regulations are not available; International Organization for Standardization, ISO5149 or European Standard, EN378 or Japan Standard, KHKS0010. ● No part of this manual may be reproduced without written permission.
  • Page 4 CHECKING PRODUCT RECEIVED ● Upon receiving this product, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. ● Check the model number, electrical characteristics (power supply, voltage and frequency) and accessories to determine if they are correct. The standard utilization of the unit shall be explained in these instructions. Therefore, the utilization of the unit other than those indicated in these instructions is not recommended. Please contact your local agent, as the occasion arises. HITACHI’s liability shall not cover defects arising from the alteration performed by a customer without HITACHI’s consent in a written form. TCI-20007-rev.1...
  • Page 5 SAFETY SUMMARY < Signal Words > ● Signal words are used to identify levels of hazard seriousness. Definitions for identifying hazard levels are provided below with their respective signal words. DANGER : DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING : WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION : CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE : NOTICE is used to address practices not related to personal injury. NOTE : NOTE is useful information for operation and/or maintenance. TCI-20007-rev.1...
  • Page 6 SAFETY SUMMARY DANGER ● Do not perform the installation work, refrigerant piping work, drain pump, drain piping and electrical wiring connection without referring to our installation manual. If the instructions are not followed, it may result in a water leakage, electric shock or fire. ● Use the specified refrigerant (R410A or R32) to the outdoor unit in the refrigerant cycle. Do not charge the unit with material other than R410A or R32, such as hydrocarbon refrigerants (propane or etc.), oxygen, flammable gases (acetylene or etc.) or poisonous gases when installing, maintaining and moving the unit. These flammables are extremely dangerous and may cause an explosion, fire, and injury. ● Do not pour water into the indoor or outdoor unit. These products are equipped with electrical parts. If water is poured, it will cause a serious electrical shock. ● Do not open the service cover or access panel for the indoor or outdoor unit without turning OFF the main power supply. ● Do not touch or adjust safety devices inside the indoor unit or outdoor unit. If these devices are touched or readjusted, it may cause a serious accident. ● Refrigerant leakage can cause difficulty with breathing due to insufficient air. Turn OFF the main switch, extinguish any naked flames and contact your service contractor, if refrigerant leakage occurs. ● Make sure that a refrigerant leak test has been performed. Refrigerant (Fluorocarbon or Difluoromethane) for this unit is non-toxic, and odorless. If the refrigerant should somehow escape and come into contact with flame, toxic gas will form. This gas is heavier than air and will settle near floor areas and spread where it can cause suffocation to those nearby. In addition, difluoromethane is flammable and can cause fire. ● The installer and system specialist shall secure safety against refrigerant leakage according to the local regulations or standards. ● Use an ELB (Earth Leakage Breaker). In the event of fault, there is danger of an electric shock or fire if it is not used. ● Do not install the outdoor unit where there is high level of oil mist, flammable gases, salty air or harmful gases such as sulfur. ● For installation, firmly connect the refrigerant pipe before the compressor starts operating. For maintenance, relocation and disposal, remove the refrigerant pipe after the compressor stops.
  • Page 7 SAFETY SUMMARY WARNING ● Do not use any sprays such as an insecticide, lacquer or hair spray, or other flammable gases within approximately one (1) meter from the system. ● If the circuit breaker or fuse is often activated, stop the system and contact your service contractor. ● Check that the ground wire is securely connected. If the unit is not correctly grounded, it will lead to electric shock. Do not connect the ground wiring to a gas piping, water piping, lighting conductor or ground wiring for telephone. ● Connect a fuse of specified capacity. ● Before performing any brazing work, check to ensure that there is no flammable material around. When handling the refrigerant, be sure to wear leather gloves to prevent cold injuries. ● Protect the wires, electrical parts, etc. from rats or other small animals. If not, rats may gnaw at unprotected parts, which may lead to a fire. ● Fix the cables securely. External forces on the terminals could lead to a fire. ● Provide a sufficiently strong foundation. If not, the unit may fall down and it may lead to injuries. ● Do not install the unit in a place where oil, vapor, organic solvent and corrosive gas (ammonia, sulfur compound and acid) may be present in quantities. It may cause refrigerant leakage due to corrosion, electrical shock, deteriorated performance and breakage. ● Perform the electrical work according to Installation Manual and all the relevant regulations and standards. If the instructions are not followed, an electrical shock and fire may occur due to insufficient capacity and inadequate performance. ● Use specified cables between units and choose the cables correctly. If not, an electrical shock or fire may occur. ● Ensure that the wiring terminals are tightened securely with the specified torques. If not, a fire or an electrical shock at the terminal connection part may occur. CAUTION ● Do not step on the product nor put any material on it.
  • Page 8 SAFETY SUMMARY NOTICE ● Do not install the indoor unit, outdoor unit, wired controller and cables within approximately 3 meters from strong electromagnetic wave radiators, such as medical equipment. ● Supply electrical power to the system to energize the crankcase heater for 12 hours before startup after a long shutdown. ● Make sure that the outdoor unit is not covered with snow or ice, before operation. ● The packaged air conditioner may not be operated normally under the following cases. * In case that electrical power for the packaged air conditioner is supplied from the same power transformer as the device with high electricity consumption*. * In case that the power source wires for the device* and for the packaged air conditioner are located close to each other. Device*: (Ex) Lift, container crane, rectifier for electric railway, inverter power device, arc furnace, electric furnace, large-sized induction motor and large-sized switch. Regarding the cases mentioned above, surge voltage may be inducted in the power supply wiring for the packaged air conditioner due to a rapid change in power consumption of the device and an activation of switch. Therefore, check the field regulations and standards before performing electrical work in order to protect the power supply for the packaged air conditioner. NOTE ● It is recommended that the room be ventilated every 3 to 4 hours. ● The heating capacity of the heat pump unit decreases according to the outdoor air temperature. Therefore, it is recommended that auxiliary heating equipment be used in the field when the units is installed in a low temperature region. TCI-20007-rev.1...
  • Page 9: Table Of Contents

    - CONTENTS - < Technical Data > 1. Features ..............................1-5 1.1 System Features ..........................1-5 1.2 Appearance ............................1-6 1.3 Features on Indoor Units ........................1-6 1.4 Features on Options .......................... 1-15 1.4.1 Wired Controller: PC-ARF1 ..................... 1-16 1.4.2 Wireless Controller: PC-AWR ....................1-17 1.4.3 7-Day Timer: PSC-A1T ......................1-18 1.4.4 Central Station: PSC-A64S ...................... 1-19 1.4.5 Central Station: PSC-5S ......................
  • Page 10 - CONTENTS - < Technical Data > 10. Control System ............................1-56 10.1 Refrigeration Cycle ..........................1-56 10.2 System Control ..........................1-57 10.2.1 Individual Operation ......................... 1-57 10.2.2 Simultaneous Operation ......................1-58 10.3 Standard Operation Sequence ......................1-59 10.4 Protection and Safety Control ......................1-74 10.5 Safety and Control Device Setting ....................1-74 10.6 Electrical Wiring Diagram ........................1-75 11. Miscellaneous Notes ..........................
  • Page 11: Technical Data

    Technical Data TCI-20007-rev.1...
  • Page 12 TCI-20007-rev.1...
  • Page 13 - CONTENTS - 1. Features ..............................1-5 1.1 System Features ..........................1-5 1.2 Appearance ............................1-6 1.3 Features on Indoor Units ........................1-6 1.4 Features on Options .......................... 1-15 1.4.1 Wired Controller: PC-ARF1 ..................... 1-16 1.4.2 Wireless Controller: PC-AWR ....................1-17 1.4.3 7-Day Timer: PSC-A1T ......................
  • Page 14 - CONTENTS - 10. Control System ............................1-56 10.1 Refrigeration Cycle ..........................1-56 10.2 System Control ..........................1-57 10.2.1 Individual Operation ......................... 1-57 10.2.2 Simultaneous Operation ......................1-58 10.3 Standard Operation Sequence ......................1-59 10.4 Protection and Safety Control ......................1-74 10.5 Safety and Control Device Setting ....................
  • Page 15: Features

    System Features New SET FREE FSR Ceiling Type Indoor Units HITACHI proudly introduces the New SET FREE FSR Ceiling Type Indoor Units, the highly-efficient and reliable air conditioning system. Recently, an increasing number of buildings are requiring "Intelligent" facilities - communication networks, office automation, as well as a comfortable environment. Particularly, a comfortable space is required all the day through the year in office buildings.
  • Page 16: Appearance

    FEATURES Appearance Features on Indoor Units Characteristic Outline Improvement of Energy Saving • High efficiency has been achieved by adopted fan (1) The energy saving has been achieved with the runner and fan motor and the performance of heat combination of current outdoor units. exchanger has also been improved.
  • Page 17 FEATURES z Improvement of Energy Saving (1) The energy saving has been achieved with the combination of current outdoor units. (2) Improvement of Energy Saving Operation by Motion Sensor * Adoption of Motion Sensor Function - The motion sensor function controls the setting temperature, air flow volume and air flow direction according to the extent of human activity.
  • Page 18 FEATURES z Wide Range Air Flow Volume Setting The number of air flow volume setting is 4 taps (HIGH 2, HIGH, MED and LOW). z Adoption of Optional Receiver Kit (PC-ALHP1) Using Receiver Kit PC-ALHP1 with wireless controller PC-AWR makes wireless remote control possible. Receiver Kit PC-ALHP1 can uses “HIGH 2.”...
  • Page 19 FEATURES Motion Sensor Control The air conditioning capacity is saved automatically depending on a situation and the amount of detected human activity by adopting the motion sensor on the corner of the lower cover. The energy saving can be improved more with the individual operating function. In addition, the operation can stop automatically if the absent situation continues for more than 30 minutes .
  • Page 20 FEATURES z Sequence of Detection by Motion Sensor Motion Sensor detects the infrared variation by sensor elements. Analog voltage is generated according to the infrared variation. Analog voltage is convert to an digital signal at the threshold. z Sequence of Controlling Motion Sensor at Indoor Unit The Indoor unit detects whether someone is present or not according to the condition of the digital signal.
  • Page 21 FEATURES z Descriptions of Motion Sensor Control Condition [Standard Condition [MODE 1] [MODE 2] [MODE 3] Operation] MENU Running on Wired “If Absent” Standby Stop Operation Controller Adjusting Forced Value of Adjusting Adjusting Adjusting Thermo- Temperature Setting [Mode3] Setting Setting Setting Same Indoor Unit...
  • Page 22 FEATURES z Wired Controller (PC-ARF1) Setting and Display The motion sensor setting can easily be set with the wired controller. The indication of “Motion Sensor ON” is displayed on the wired controller LCD during controlling the motion sensor. ● Sensor LCD Indication during Setting ON: The operating control function by the motion sensor is activated.
  • Page 23 FEATURES z Cooling/Heating Auto Changeover Dual Setpoint Control This function is utilized to change cooling and heating operation automatically (the same operation mode for indoor units in the same refrigerant cycle) depending on both cooling setpoint and heating setpoint (dual setpoint).
  • Page 24 FEATURES z Setback Temperature Control Setback Temperature Control is mainly to sustain a comfort room air temperature while occupants are out of the room. Four features are shown below: Mode Usage Example At hotel rooms, the Setback Temperature Control will be activated when the card key is Setback Input taken out.
  • Page 25: Features On Options

    FEATURES Features on Options HITACHI provides the optional accessories for indoor units. RPC-FSR PC-AR Wired Controller PC-ARF1 (*1) Wireless Controller PC-AWR (*1) 7-Day Timer PSC-A1T PSC-A64S (*2) PSC-5S (*2) Central Station PSC-A64GT PSC-A32MN Central Station DX PSC-A128WX2 + PSC-AS2048WXB2 Central Station NT...
  • Page 26: Wired Controller: Pc-Arf1

    FEATURES 1.4.1 Wired Controller: PC-ARF1 Model: PC-ARF1 Following is an example of how the PC-ARF1 is utilized. If other models of the controller are utilized, operate the unit according to the manual for that controller. The example below references the control panel and all adjustable settings.
  • Page 27: Wireless Controller: Pc-Awr

    FEATURES 1.4.2 Wireless Controller: PC-AWR Model: PC-AWR Reset Switch Transmitter Point the transmitter towards the receiver of the indoor unit when sending commands. The transmitting indication on the liquid crystal display flashes when sending commands. Transmitting Indication: It will turn ON when sending commands by infrared rays. LCD (Liquid Crystal Display) The set temperature, timer operation, position of air louver, operation mode, air flow mode, etc., are indicated.
  • Page 28: 7-Day Timer: Psc-A1T

    FEATURES 1.4.3 7-Day Timer: PSC-A1T Model: PSC-A1T By plugging this timer into the optional wired controller, daily ON/OFF operation control throughout the week is available. 7-Day Timer has power failure back-up dry cell. The ON/OFF control is available three times a day at a maximum and the ON/OFF time can be set by the minute.
  • Page 29: Central Station: Psc-A64S

    FEATURES 1.4.4 Central Station: PSC-A64S Model: PSC-A64S Liquid Crystal Display Selection The figure below shows all the indications for reference. The actual display during operation is different. Indication of Indication of Indication of Indication of Setting Setting Target Timer Demand Control Temperature Indication of Indication of Emergency Stop...
  • Page 30: Central Station: Psc-5S

    FEATURES 1.4.5 Central Station: PSC-5S Model: PSC-5S This central station is of the soft touch type. (Operation except with finger is not recommended.) Activation can be checked by referring to the liquid crystal display and LEDs. The figure below shows all the indications for reference. Liquid Crystal Display Section The actual display during operation is different.
  • Page 31: Central Station: Psc-A64Gt

    FEATURES 1.4.6 Central Station: PSC-A64GT Model: PSC-A64GT Touch Pen To operate the touchscreen of the central station. Color LCD Display with Touchscreen Power Indicator To operate and monitor the units on the touchscreen To indicate the power condition of display. It is operated by using touch pen (accessory). the central station.
  • Page 32 FEATURES z System Example (PSC-A64GT) This central station (PSC-A64GT) is connected to H-LINK and used for the central control and monitoring of the air conditioners. The system configuration example is shown below. Max. 64 Remote Control Groups and Max. 160 Indoor Units are available. (For H-LINK II Only) Terminal Resistance Setting DSW5 Refrigerant No.
  • Page 33: Central Station: Psc-A32Mn

    FEATURES 1.4.7 Central Station: PSC-A32MN Model: PSC-A32MN Touch Pen To operate the touchscreen of the central station. Color LCD Display with Touchscreen Power Indicator To operate and monitor the units by the touchscreen To indicate the power condition of display. It is operated by using touch pen (accessory). the central station.
  • Page 34: Central Station Dx: Psc-A128Wx2, Psc-As2048Wxb2

    FEATURES 1.4.8 Central Station DX: PSC-A128WX2, PSC-AS2048WXB2 Product Name Model Central Station DX: Adapter PSC-A128WX2 Central Station DX: Management Software PSC-AS2048WXB2 (1) Managing Maximum 2048 Groups (2560 Indoor Units) of Air Conditioners Up to 2560 units of Air Conditioners can be controlled and monitored by one computer. (2) Improved Operability by Tree View and Simple Schedule Setting •...
  • Page 35 FEATURES < Example for System Configuration > (Not in the package) Management computer (Not in the package) (Not in the package) Indoor unit Indoor unit Indoor unit LAN(Ethernet) PSC-A128WX2 Outdoor unit Outdoor unit Management software PSC-AS2048WXB2 External input points (Up to 3) (Not included in the package) External output points (Up to 3) Outdoor unit...
  • Page 36: Central Station Nt: Psc-A128Web3

    FEATURES 1.4.9 Central Station NT: PSC-A128WEB3 Model: PSC-A128WEB3 (1) Easy-to-View and Operable Screen ● User-friendly screen is achieved by laying out whole configuration of the air conditioning system in one window. Tree of Blocks and Groups can be displayed in a pop-up window . ●...
  • Page 37 FEATURES < Example for System Configuration > A4 Page Printer (Field-Supplied) (Field-Supplied) Computer Computer (Field-Supplied) (Field-Supplied) Router Router Internet (Field-Supplied) (Field-Supplied) (Field-Supplied) (Field-Supplied) Power Line LAN(Ethernet ® Indoor unit Indoor unit Indoor unit PSC-A128WEB3 Power Line External input points (Up to 8) Outdoor unit Outdoor unit External output points (Up to 3)
  • Page 38: Central Station Ex: Psc-A128Ex

    FEATURES 1.4.10 Central Station EX: PSC-A128EX Model: PSC-A128EX Product Name Model Central Station EX: PSC-A128EX Extension Adapter: PSC-AD128EX *1 Energy Calculation Software: PSC-AS01EXC *2 *1: Required only when the system consists of multiple H-LINKs *2: Required only for calculating electricity (1) Management of up to 2,048 groups (2,560 indoor units)* This product alone can monitor and control air conditioners.
  • Page 39 FEATURES ● Central Station EX: PSC-A128EX (Unit: mm) 32.5 27.8 SD Card Slot USB flash drive slot H-LINK, External in/output Wiring Port LAN Port Power Input ● Extension Adapter: PSC-AD128EX (Unit: mm) 255.6 235.6 Status Indicator Screw Hole for Wall Mount Power Button (Remove rubber cover.) H-LINK, External in/output, and LAN Wiring Port...
  • Page 40 FEATURES < Example for System Configuration > Power Line Pulse Transmission Meter (Field-Supplied) Pulse Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit Transmission Meter Power Line (Field-Supplied) External Device (Demand Controller, External Lighting, etc.) Input Line (Field-Supplied) Extension Adapter (PSC-AD128EX)
  • Page 41: Centralized On/Off Controller: Psc-A16Rs

    FEATURES 1.4.11 Centralized ON/OFF Controller: PSC-A16RS Model: PSC-A16RS Simultaneous RUN/STOP Switch This switch is for ordering the simultaneous operation / stoppage to all groups. Depressing this switch when there is any group in operation, all the group is stopped simultaneously. Depressing this switch when all the group is stopped, all the group starts operation simultaneously.
  • Page 42: H-Link Relay: Psc-5Hr

    FEATURES 1.4.12 H-LINK Relay: PSC-5HR 8 Holes: φ6 < System Configuration > Four H-LINK Relays can be installed at a maximum. H-LINK is divided into blocks by H-LINK relay. The number of connectable refrigerant cycles and indoor units is limited as shown below. <Compared with H-LINK System>...
  • Page 43: Motion Sensor Kit: Sor-Nep

    FEATURES 1.4.13 Motion Sensor Kit: SOR-NEP 49.5 Connect the wiring for Motion Sensor Kit to the connector CN10 on the indoor unit PCB in the electrical box. 2 Wired Controller Covers Lower Cover Position for Motion Sensor Kit (It can be attached to both right and left sides.) NOTES: 1.
  • Page 44 FEATURES Length of Wire Cable for Optional Wired Controller, Timer and Central Station As the wired controllers, timer and central stations do not include a controller cable, prepare one in the field, or use PRC-5K, 10K or 15K. Use the twist pair cable (1P-0.75mm ) as transmission wire cable for prevention of the malfunction (The total cable length is max.
  • Page 45: General Data

    GENERAL DATA 2. General Data Indoor Unit Type Ceiling Type Model RPC-1.5FSR RPC-2.0FSR RPC-2.5FSR RPC-3.0FSR Indoor Unit Power Supply AC 1, 220-240V/50Hz, 220V/60Hz Sound Pressure Level (Overall A Scale) (Hi2/Hi/Me/Lo) 37/35/31/28 38/35/31/28 38/35/31/28 40/37/33/29 Cabinet Color Neutral White Outer Dimensions Height (in.)
  • Page 46: General Data

    GENERAL DATA Indoor Unit Type Ceiling Type Model RPC-4.0FSR RPC-5.0FSR RPC-6.0FSR Indoor Unit Power Supply AC 1, 220-240V/50Hz, 220V/60Hz Sound Pressure Level (Overall A Scale) (Hi2/Hi/Me/Lo) 44/42/37/32 48/45/41/35 49/47/42/36 Cabinet Color Neutral White Outer Dimensions Height (in.) (9-1/4) (9-1/4) (9-1/4) Width 1580 1580...
  • Page 47: Dimensional Data

    DIMENSIONAL DATA 3. Dimensional Data Models: RPC-1.5FSR and RPC-2.0FSR 1-37 TCI-20007-rev.1...
  • Page 48 DIMENSIONAL DATA Models: RPC-2.5FSR and RPC-3.0FSR 1-38 TCI-20007-rev.1...
  • Page 49 DIMENSIONAL DATA Models: RPC-4.0FSR, RPC-5.0FSR and RPC-6.0FSR 1-39 TCI-20007-rev.1...
  • Page 50: Selection Data

    SELECTION DATA 4. Selection Data Operation Space (mm) Min. Min. 40 Min. 8 Min. Min. 400 Minimum service space Minimum service space to for auto louver motor Min. tighten the suspension bolt 2500 Floor Level < For Single Installation > (mm) Min.
  • Page 51: Selection Guide

    SELECTION DATA Selection Guide The various indoor units can be combined with the HITACHI DC Inverter UTOPIA Series. Selection of Unit Model Capacity Procedure is shown below. Calculate Heating Load on Each Room Select Indoor Unit Capacity Select Outdoor Unit Capacity Check Unit Capacity Rated Capacity of Outdoor Unit >...
  • Page 52 16.0 18.0 Capacity Adjustment by Dip Switch Setting Horsepower (HP) Variable Capacity (HP) Nominal Cooling Capacity Nominal Heating Capacity Applicable Model RPC-1.5FSR RPC-2.0FSR RPC-2.5FSR 1.5HP 2.0HP 2.5HP 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6...
  • Page 53 Actual Capacity of Each Indoor Unit = Actual Capacity of Outdoor Unit 5 (Each Indoor Unit's Horsepower ÷ Summation of Each Indoor Unit Horsepower) < RPC-1.5FSR > Cooling Capacity: 14.11 5 (1.5HP/6.0HP) = 3.53kW Heating Capacity: 14.05 5 (1.5HP/6.0HP) = 3.51kW <...
  • Page 54: Air Throw Distance

    Air Throw Air Flow Ceiling Height Distance Volume Height Model /min) of Ceiling RPC-1.5FSR Air Direction RPC-2.0FSR RPC-2.5FSR RPC-3.0FSR RPC-4.0FSR RPC-5.0FSR RPC-6.0FSR NOTES: 1. The air throw distance is a distance the outlet air blowing from the air outlet obliquely downward reaches.
  • Page 55: Electrical Data

    ELECTRICAL DATA 5. Electrical Data < 220-240V/50Hz > Unit Main Power Applicable Voltage Indoor Fan Motor Model Maximum Minimum RPC-1.5FSR 0.2-0.2 0.04-0.04 RPC-2.0FSR 0.2-0.3 0.05-0.05 RPC-2.5FSR 0.2-0.3 0.05-0.05 RPC-3.0FSR 220-240 0.3-0.3 0.06-0.06 RPC-4.0FSR 0.5-0.5 0.10-0.10 RPC-5.0FSR 0.8-0.9 0.16-0.16 RPC-6.0FSR 0.9-1.0 0.19-0.19...
  • Page 56: Sound Data

    SOUND DATA 6. Sound Data 1-46 TCI-20007-rev.1...
  • Page 57 SOUND DATA 1-47 TCI-20007-rev.1...
  • Page 58: Working Range

    WORKING RANGE 7. Working Range Power Supply Working Voltage: 90% to 110% of the Rated Voltage Voltage Imbalance: Within a 3% Deviation from Each Voltage at the Main Terminal Starting Voltage: Higher than 85% of the Rated Voltage Temperature Range The temperature range are given in the following table.
  • Page 59: Optional Accessories

    OPTIONAL ACCESSORIES 8. Optional Accessories for Control Systems HITACHI provides the optional accessories for indoor units. RPC-FSR PC-AR Wired Controller PC-ARF1 (*1) Wireless Controller PC-AWR (*1) 7-Day Timer PSC-A1T PSC-A64S (*2) PSC-5S (*2) Central Station PSC-A64GT PSC-A32MN Central Station DX...
  • Page 60: Wired Controller: Pc-Arf1

    OPTIONAL ACCESSORIES 8.1.1 Wired Controller: PC-ARF1 Refer to chapter 1.4.1 for details. 8.1.2 Wireless Controller: PC-AWR Refer to chapter 1.4.2 for details. 8.1.3 7-Day Timer: PSC-A1T Refer to chapter 1.4.3 for details. 8.1.4 Central Station: PSC-A64S Refer to chapter 1.4.4 for details. 8.1.5 Central Station: PSC-5S Refer to chapter 1.4.5 for details.
  • Page 61: Controller Cable: Prc-5K To 15K (For Wired Controllers And Central Stations)

    OPTIONAL ACCESSORIES 8.1.14 Controller Cable: PRC-5K to 15K (for Wired Controllers and Central Stations) As the wired controllers and central stations do not include a controller cable, use PRC-5K to 15K, or prepare one in the field. Outer Diameter φ7 0.75mm JIS 1.25-3x Model Cable Length PRC-5K PRC-10K...
  • Page 62: For Ceiling Type

    OPTIONAL ACCESSORIES for Ceiling Type 8.2.1 Long Life Filter: F-56LPC1, F-90LPC1 and F-160LPC1 Long Life Filter (mm) Model Small Large 10.5 10.5 Specifications The following specifications are for air filters attached to the indoor units as standard equipment. Model F-56LPC1 F-90LPC1 F-160LPC1 Item Applicable Indoor Unit Model 1.5 and 2.0 2.5 and 3.0 4.0 to 6.0 (RPC-**FSR) Small Required Quantity per...
  • Page 63: Drain-Up Mechanism: Dupc-63K1, Dupc-71K1 And Dupc-160K1

    OPTIONAL ACCESSORIES 8.2.2 Drain-Up Mechanism: DUPC-63K1, DUPC-71K1 and DUPC-160K1 The dimension of Drain-Up Mechanism attached to the indoor unit is shown with shaded portions in the figure below. Refer to Installation and Maintenance Manual attached to the product for details on its installation and use. Dimension View from Upper Side >8 (Service Space) Electrical Front Side Air Conditioner Rear Side (Indoor Unit)
  • Page 64: Motion Sensor Kit: Sor-Nep

    OPTIONAL ACCESSORIES For Ceiling Type Model Item DUPC-63K1 DUPC-71K1 DUPC-160K1 Applicable Indoor Unit Model (RPC-**FSR) 2.5 to 6.0 Maximum Lift for Drain-Up 600 (from the upper side of the indoor unit) Power Source DC13V Power Consumption 4.2 or less Drain Piping Connection PVC Tube, VP25 Diameter of 12.7...
  • Page 65: Component Data

    COMPONENT DATA 9. Component Data Indoor Heat Exchanger and Fan Model RPC-1.5FSR RPC-2.0FSR RPC-2.5FSR RPC-3.0FSR Heat Exchanger Type Multi-Pass Cross Finned Tube Tube Material Copper Tube Outer Diameter Rows Number of Tube/Coil Fin Material Aluminum Pitch Maximum Operating Pressure 4.15 4.15...
  • Page 66 CONTROL SYSTEM 10. Control System 10.1 Refrigeration Cycle Models: RPC-1.5FSR, RPC-2.0FSR, RPC-2.5FSR, RPC-3.0FSR, RPC-4.0FSR, RPC-5.0FSR and RPC-6.0FSR Indoor Unit : Refrigerant Flow Direction (Cooling Operation) : Refrigerant Flow Direction (Heating Operation) : Field Refrigerant Piping : Flare Connection Refrigerant Gas Pipe Connection...
  • Page 67: Control System

    CONTROL SYSTEM 10.2 System Control 10.2.1 Individual Operation Control Wiring (H-LINK II) Indoor Unit Outdoor Unit Wired Controller (PC-ARF1) < Individual Thermo ON/OFF Operation > The individual Thermo ON/OFF operation for each indoor unit is available even if multiple indoor units are controlled simultaneously by one wired controller.
  • Page 68: Simultaneous Operation

    CONTROL SYSTEM 10.2.2 Simultaneous Operation n Combination with DC Inverter UTOPIA Series Outdoor Unit This unit can be operated simultaneously with twin, triple and quad combinations. One wired controller (PC-ARF1) can control without transition wiring up to 4 units of FSN2 series or later model types (H-LINK II-supporting models) simultaneously.
  • Page 69: Standard Operation Sequence

    CONTROL SYSTEM 10.3 Standard Operation Sequence Each of the following operation sequences is just one example when the unit is combined with DC Inverter UTOPIA Series Outdoor Unit. n Cooling Operation I.U.: Indoor Unit O.U.: Outdoor Unit < 75 Power to Power to Temp.
  • Page 70 CONTROL SYSTEM n Cooling Operation I.U.: Indoor Unit O.U.: Outdoor Unit Inverter: OFF MC Operation: OFF Temp. at Top < Td Target Temp. - 15 Power to CH : ON of Compressor > Td Target Temp. - 10 Power to CH : OFF Press RUN/STOP MOF Operation: OFF...
  • Page 71 CONTROL SYSTEM n Dry Operation I.U.: Indoor Unit O.U.: Outdoor Unit Power to Temp. at Top < 75 Power to Power to CH : ON of Compressor O.U. PCB: ON O.U.: ON > 75 Power to CH : OFF Auto-Louver only for indoor unit 0 Reset with auto-louver...
  • Page 72 CONTROL SYSTEM n Dry Operation I.U.: Indoor Unit O.U.: Outdoor Unit Inverter: OFF MC Operation: OFF < Td Target Temp. - 15 Temp. at Top Power to CH : ON of Compressor > Td Target Temp. - 10 Power to CH : OFF Press RUN/STOP MOF Operation: OFF...
  • Page 73 CONTROL SYSTEM n Heating Operation I.U.: Indoor Unit O.U.: Outdoor Unit < 75 Power to Power to Temp. at Top Power to CH : ON of Compressor O.U.: ON O.U. PCB: ON > 75 Power to CH : OFF Start of Transmission between Power to Power to O.U.
  • Page 74 CONTROL SYSTEM n Heating Operation I.U.: Indoor Unit O.U.: Outdoor Unit < Set Temp. + 2 I.U. Air Heating Intake Operation Temp. Control of MC Frequency > Set Temp. +2 (including Stop) Control of MOF Fan Speed Thermo-OFF (including Stop) >...
  • Page 75 CONTROL SYSTEM n Automatic Cooling and Heating Operation It is applicable only for single. Auto Cooling/Heating I.U.: Indoor Unit Operation I.U. Air < Set Temp. Intake Temp. > Set Temp. Cooling Heating Operation Operation I.U. Air I.U. Air Intake Intake >...
  • Page 76 CONTROL SYSTEM n Defrosting Operation I.U.: Indoor Unit Power to Heating RVR : OFF Operation “DEFROST” Indication Defrosting MIF Operation: OFF Start Condition is approved. MOF Operation: OFF Power to Defrosting RVR : ON Operation “DEFROST” Indication Defrosting : OFF Stop Condition is approved.
  • Page 77 CONTROL SYSTEM <Condition for Starting Defrost> (1) Standard Defrost (a) Temperature Condition Defrosting Outdoor Operation Evaporating Stop Area Temp. ( Temperature (Pipe) Condition under Defrosting Outdoor Operation Temp. ( -6.7 Defrosting Operation Start Area (b) Condition for Operating Time of Defrosting Operation Start The defrosting operation starts when the temperature condition shown in “(a) Temperature Condition” is met after the heating operation is performed for 40 to 120 minutes. The heating operation time is determined by estimating the amount of frost on the heat exchanger.
  • Page 78 CONTROL SYSTEM n Freezing Protection Control during Cooling or Dry Operation I.U.: Indoor Unit Power Supply Cooling Operation Is compressor operated for more than 30 min. *1): The check interval differs depending on the conditions. Cooling Operation Gas or Liquid Pipe >...
  • Page 79 CONTROL SYSTEM n Prevention Control for High Pressure Increase during Cooling Operation This function is performed to prevent the abnormal condition (Alarm Code: 02) when the air flow volume decreases due to a seasonal wind against air outlet of the outdoor unit. When the following conditions are met, the forced Thermo-OFF operation will be performed. The cause of stoppage will be “13” during Thermo-OFF. Y52C is turned “ON” during the cooling operation, or is turned “ON” (during the compressor...
  • Page 80 CONTROL SYSTEM n Prevention Control for Excessively High Discharge Gas Temperature I.U.: Indoor Unit Heating Operation I.U. Air < 65 Outlet Temp. > 65 CMC : OFF Compressor: Elapsed Time: 3 min. I.U. Air > 65 Outlet Temp. < 65 Set Temp.
  • Page 81 CONTROL SYSTEM n Control for Crankcase Heater < During Stopping Compressor > < During Operating Compressor > O.U.: Outdoor Unit Power to O.U.: ON Compressor: ON > 75 Temp. at Top Temp. at Top of Compressor of Compressor > Target Temp. - 15 <...
  • Page 82 CONTROL SYSTEM n Actuation for Protection Instrument I.U.: Indoor Unit O.U.: Outdoor Unit Operation Excessively High FS : YH2 : MD Operation: ON Drain Water Level Contact is closed. Contact is opened. Activation of Protection Device RUN indicator Flashes for I.U. PCB Excessively High MIF Operation: OFF ITI : Opened...
  • Page 83 CONTROL SYSTEM n Control for Motion Sensor Following is only one example. The sequence may be different depending on the outdoor unit model to be connected. Refer to the “Outdoor Unit Technical Catalog” for details. Motion Sensor : OFF Operation: OFF Operation Stop Operation Start Normal Operation Motion Sensor Setting of Motion Sensor Setting of Wired Controller: Wired Controller: Operation Stop OFF or Test Run Mode ON and Not Test Run Mode Motion Sensor : ON The condition with no human activity...
  • Page 84: Protection And Safety Control

    Crankcase Heater - This band type heater protects against oil Carry-over during cold starting, as it is energized while the compressor is stopped. 10.5 Safety and Control Device Setting < Indoor Unit > RPC-1.5FSR, RPC-2.0FSR, RPC-2.5FSR, RPC-3.0FSR, Model RPC-4.0FSR, RPC-5.0FSR, RPC-6.0FSR For Evaporator Fan Motor Internal Thermostat...
  • Page 85: Electrical Wiring Diagram

    CONTROL SYSTEM 10.6 Electrical Wiring Diagram ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPC-1.5FSR, RPC-2.0FSR, RPC-2.5FSR, RPC-3.0FSR, RPC-4.0FSR, RPC-5.0FSR AND RPC-6.0FSR) 1-75 TCI-20007-rev.1...
  • Page 86 CONTROL SYSTEM 1-76 TCI-20007-rev.1...
  • Page 87: Miscellaneous Notes

    MISCELLANEOUS NOTES 11. Miscellaneous Notes Special Notes 1. Provide a service access door near the unit 10. During heating operation, the outdoor heat piping connection part on the false ceiling for the exchanger produces condensate dew ceiling type units. condensation or melted frost water. 2.
  • Page 88: Standard Specifications

    STANDARD SPECIFICATIONS 12. Standard Specifications UNIT - The unit shall be a multi-split system inverter- OUTDOOR UNIT driven heat pump air conditioner for application with CABINET - The cabinet shall be constructed of R410A or R32 refrigerants, and shall be composed of ceiling type indoor units and an outdoor unit, with a galvanized steel sheet, baked with synthetic resin distributed refrigeration cycle, electrical components...