Ld0.Eflptoc2 Non-Directional Earth-Fault And Sensitive Earth-Fault Protection - Low Stage 2; Ld0.Phiptoc2 Phase Overcurrent Protection; Instantaneous Stage 2; Ld0.Phiptoc1 Phase Overcurrent Protection - Instantaneous Stage 1 - ABB Relion 615 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS756883 C
2.3.1.39
Table 42:

LD0.EFLPTOC2 Non-directional earth-fault and sensitive earth-fault protection - low stage 2

IEC 61850 name
SA name
LD0.EFLPTOC2
.Op.general
OPERATE
.Str.general
START
2.3.1.40
Table 43:
LD0.PHIPTOC2 Phase overcurrent protection - instantaneous stage 2
IEC 61850 name
SA name
LD0.PHIPTOC2
.Str.phsA
-
.Str.phsB
-
.Str.phsC
-
.Str.general
START
.Op.general
OPERATE
2.3.1.41
Table 44:

LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1

IEC 61850 name
SA name
LD0.PHIPTOC1
.Str.phsA
-
.Str.phsB
-
.Str.phsC
-
.Str.general
START
.Op.general
OPERATE
2.3.1.42
Table 45:

LD0.PHHPTOC2 Phase overcurrent protection - high stage 2

IEC 61850 name
SA name
LD0.PHHPTOC2
.Str.phsA
-
.Str.phsB
-
.Str.phsC
-
.Str.general
START
.Op.general
OPERATE
RET615
Point List Manual
LD0.EFLPTOC2 Non-directional earth-fault and sensitive earth-fault
protection - low stage 2
Description
Low (2) stage
-operate
-start
LD0.PHIPTOC2 Phase overcurrent protection - instantaneous stage 2
Description
Instantaneous stage (2)
-phsA start
-phsB start
-phsC start
-general start
-general operate
LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1
Description
Instantaneous stage (1)
-phsA start
-phsB start
-phsC start
-general start
-general operate
LD0.PHHPTOC2 Phase overcurrent protection - high stage 2
Description
High stage (2)
-phsA start
-phsB start
-phsC start
-general start
-general operate
IEC 60870-5-103 data mappings
DPI value
FUN
10=Operate
159
10=Start
159
DPI value
FUN
10=Start
162
10=Start
162
10=Start
162
10=Start
162
10=Operate
162
DPI value
FUN
10=Start
162
10=Start
162
10=Start
162
10=Start
162
10=Operate
162
DPI value
FUN
10=Start
162
10=Start
162
10=Start
162
10=Start
162
10=Operate
162
Section 2
INF
U
ASDU
I
C
91
1
2
0
1
94
1
2
1
1
INF
U
ASDU
I
C
24
0
2
1
1
25
0
2
1
1
26
0
2
1
1
102
1
2
1
1
103
1
2
0
1
INF
U
ASDU
I
C
34
0
2
1
1
35
0
2
1
1
36
0
2
1
1
97
1
2
1
1
99
1
2
0
1
INF
U
ASDU
I
C
44
0
2
1
1
45
0
2
1
1
46
0
2
1
1
96
1
2
1
1
98
1
2
0
1
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ret615

Table of Contents