Ld0.Nsptoc1 Negative-Sequence Overcurrent Protection (1); Ld0.Nsptoc2 Negative-Sequence Overcurrent Protection (2); Ld0.Seqrfuf1 Fuse Failure Protection; Ld0.Tpossltc1 Tap Position - ABB Relion 615 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 2
IEC 60870-5-103 data mappings
2.3.1.10
Table 13:

LD0.NSPTOC1 Negative-sequence overcurrent protection (1)

IEC 61850 name
SA name
LD0.NSPTOC1
.Str.general
START
.Op.general
OPERATE
2.3.1.11
Table 14:

LD0.NSPTOC2 Negative-sequence overcurrent protection (2)

IEC 61850 name
SA name
LD0.NSPTOC2
.Op.general
OPERATE
.Str.general
START
2.3.1.12
Table 15:

LD0.SEQRFUF1 Fuse failure protection

IEC 61850 name
SA name
LD0.SEQRFUF1
.Str.general
FUSEF_U
.Str3Ph.general
FUSEF_3PH
2.3.1.13
Table 16:

LD0.TPOSSLTC1 Tap position

IEC 61850 name
SA name
LD0.TPOSSLTC1
.ValWTr.posVal
TAP_POS
2.3.1.14
Table 17:

LD0.MAPGAPC1 Multipurpose analog protection function (1)

IEC 61850 name
SA name
LD0.MAPGAPC1
.Str.general
START
.Op.general
OPERATE
18
LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
Description
Stage1 start
Stage1 operate
LD0.NSPTOC2 Negative-sequence overcurrent protection (2)
Description
Stage2 operate
Stage2 start
LD0.SEQRFUF1 Fuse failure protection
Description
General start
3 phase start
LD0.TPOSSLTC1 Tap position
Description
Tap position
LD0.MAPGAPC1 Multipurpose analog protection function (1)
Description
Stage Start
Stage Operate
DPI value
FUN
10=Start
21
10=Operate
21
DPI value
FUN
10=Operate
21
10=Start
21
DPI value
FUN
10=Start
22
10=Start
22
DPI value
FUN
Value -64...63
25
DPI value
FUN
10=Start
27
10=Operate
27
1MRS756883 C
INF
U
ASDU
I
C
84
1
2
1
1
90
1
2
0
1
INF
U
ASDU
I
C
91
1
2
0
1
94
1
2
1
1
INF
U
ASDU
I
C
84
1
2
1
1
94
1
2
1
1
INF
U
ASDU
I
C
20
1
4
1
-
INF
U
ASDU
I
C
151
1
1
1
1
152
1
1
0
1
RET615
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ret615

Table of Contents