Honeywell S8600B Installation Instructions Manual page 14

Intermittent pilot gas ignition control
Hide thumbs Also See for S8600B:
Table of Contents

Advertisement

S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL
Table 7. Lockout Models B, H D, and J Only—Green LED Status Codes. (Continued)
Green LED
a
Flash Code
7
Flame rod shorted to ground
8
Low secondary voltage supply Control remains in wait mode. When the fault
a
Flash Code Descriptions:
- Flash Fast: rapid blinking.
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- 4 second solid on pulse followed by "x" 1 second flashes indicates flame current to the nearest A. This is only
available in run mode.
- A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then
repeats the sequence.
Flame Current Measurement
Flame current of the device can be meaured using a
standard micro-ammeter by simply inserting the meter
probes into the holes labeled FLAME CURRENT, as
shown in Fig. 13.
Flame current must be measured with pilot valve
lit but no main gas flowing.
Disconnect MV leadwire from the control before
measuring flame current.
Set meter to DC Amp scale.
Ensure meter leads are positioned correctly [+/-].
WARNING
!
Explosion Hazard.
Can cause serious injury or death.
This device can malfunction if
it gets wet. Never try to use a
device that has been wet - replace it.
69-1954—01
บริ ษ ั ท เอดี ด ี เฟอร์ เ นส จํ า กั ด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258
https://www.add-furnace.com E-mail: sales@add-furnace.com
Indicates
Control remains in wait mode. When the fault
corrects, control resumes normal operation.
corrects, control resumes normal operation.
Golden Valley, MN 55422
Assembled in Mexico
S8600M Continuous Retry
24V, 60 Hz; PV=1A Max.; MV=1A Max.
LED FLAME INDICATION:
90 Sec. Trial for Ignition
- 4 sec. pulse then 1 sec. flashes
indicate flame current in uA:
= 3 uA
®
- Ensure 1 uA to
avoid loc
kout
C
US
50043739-003 Rev. A
ANSI Z21.20
LED FLASH CODES:
retry
(2)
recycle
(3)
flame out of sequence
(4)
internal error
(6)
flame rod shorted
(7)
low input voltage
(8)
+
FLAME
CURRENT
STATUS
+
FLAME
CURRENT
Fig. 13. Measuring pilot flame current with micro-ammeter.
Next System Action
NOTE: Trying to measure the pilot flame current in
series with the wiring will not be accurate.
Recommended Minimum Pilot Only Flame Current:
• Must read steady 1 Amp DC minimum.
• Flame current should be 2 Amp or greater for reliable
appliance operation.
SPARK
STATUS
14
Recommended Service Action
Check flame sense lead wire for damage or
shorting. Check that flame rod is in proper
position.Check flame rod ceramic for cracks,
damage or tracking.
Check transformer and AC line for proper
input voltage to the control. Check with full
system load on the transformer.
.
DC
A
M31297