H2 Extension Module; Output Ux - Siemens Albatros2 User Manual

Heat pump controller
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

H2 extension module

10V output UX
Function output UX
Siemens Switzerland Ltd
HVAC Products
Line no.
Operating line
6046
Function input H2
Optg mode changeover HCs+DHW
Optg mode changeover HCs
Optg mode changeover HC1
Optg mode changeover HC2
Optg mode changeover HCP
Error/alarm message
Minimum flow temp setpoint
Heat request 10V
Dewpoint monitor
Flow temp setp incr hygro
Refrigeration request
Refrigeration request 10V
Pressure measurement 10V
Rel room humidity 10V
Room temp 10V
Release swimming pool
Switch-on command HP stage 1
Switch-on command HP stage 2
6047
Contact type H2
NC
NO
6048
Function value, contact H2
6049
Voltage value 1 H2
6050
Function value 1 H2
6051
Voltage value 2 H2
6052
Function value 2 H2
The settings for input H2 on the extension module are the same as those for the Hx
inputs on the basic unit. They are described under operating line "Function input Hx".
Line no.
Operating line
6070
Function output UX
None
Source pump Q8 / fan K19
DHW pump Q3
DHW interm circ pump Q33
Instant DHW heater Q34
Collector pump Q5
Collector pump 2 Q16
Solar pump buffer K8
Solar pump ext exch K9
Solar pump swi pool K18
Heat circ pump HC1 Q2
Heat circ pump HC2 Q6
Heat circ pump HCP Q20
HP setpoint
Output setpoint
Heat request
Refrigeration request
6071
Signal logic output UX
Standard
Inverted
6072
Signal output UX
0...10V
PWM
6075
Temp value 10V UX
The voltage-modulated output can be used either for speed-controlled pumps or as an
output for a voltage-proportional temperature request.
User manual RVS61.843
6 The settings in detail
159/221
CE1U2355en_02
23. November 2007