Stratification Protection; Overtemperature Protection - Siemens Albatros2 User Manual

Heat pump controller
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

Stratification protection

Overtemperature protection

Siemens Switzerland Ltd
HVAC Products
Locked
The heat source is locked as soon as the temperature at both buffer storage tank
sensors drops by less than "Temp diff buffer/HC" below the required flow temperature.
T
4722
B41
1K
ON
K
OFF
4722
Temp diff buffer/HC
B4
Upper buffer or combi storage tank sensor
B41
Lower buffer or combi storage tank sensor
TVLw
Flow temperature setpoint
K
Compressor
Using "Temp diff buffer/HC", the mixing valve boost resulting from the heating circuit's
temperature request can be compensated.
Line no.
Operating line
4739
Stratification protection
Aus ¦ Immer
The buffer storage tank's stratification protection function provides for hydraulic
balancing between the consumers and the heat source without the need for additional
shutoff valves for the buffer storage tank.
When the function is active, the volume of water on the consumer side is adjusted so
that, where possible, the addition of colder water from the buffer storage tank is
avoided.
Off :
Stratification protection is switched off.
Always :
Stratification protection is active when the heat source
is on.
A common flow sensor B10 must be connected for this
function.
Line no.
Operating line
4750
Charging temp max
Solar energy charges the buffer storage tank until the set maximum charging
temperature is reached.
The protective collector overtemperature function can reactivate the collector pump
until the maximum storage tank temperature is reached.
User manual RVS61.843
6 The settings in detail
TVLw
B4
OFF
ON
t
131/221
CE1U2355en_02
23. November 2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents