Relay modules with valve proving
Table of Contents

Advertisement

Item
Description
V1
Upstream Valve Volume
V2
Downstream Valve Volume
D
Pipe Size NPT (in.)
L
Pipe Length (ft)
P
Valve Inlet Pressure (psig)
C
Burner Maximum Firing (cf/hr)
a
Divide inches w.c. by 27.7 to get psi.
b
Divide Btuh by 1000 to get cf/hr for natural gas or by 2550 to get cf/hr for LP gas.
Calculation of Valve Train Volume:
X = V1 + V2 + (A x L ÷ 144)
X = 0.0218 + 0.0267 + (3.356 x 1.75 ÷ 144) = 0.0893.
Calculation of Valve Proving Test Time:
Pipe Size
NPT (inches)
V4295
3/8
0.0002
1/2
0.0002
3/4
0.0008
1
0.0009
1-1/4
0.0045
1-1/2
0.0045
2
0.0089
2-1/2
0.0441
3
0.0441
4
Pipe Size
NPT (inches)
V4295
3/8
0.0011
1/2
0.0011
3/4
0.0026
1
0.0036
1-1/4
0.0148
1-1/2
0.0148
2
0.0267
2-1/2
0.0554
3
0.0554
4
Table 12. VPS Worksheet Example.
Information
V5055
V4295
2 in. NPT
1.75 ft
2
a
b
2.5 mbtu
Table 13. V1 Upstream Volumes for Honeywell Valves.
V4297A1013 V4297A1005
0.0093
0.0090
0.0093
0.0090
0.0093
0.0090
0.0093
0.0093
Table 14. V2 Downstream Volumes for Honeywell Valves.
V4297A1013 V4297A1005
0.0282
0.0232
0.0282
0.0232
0.0282
0.0232
0.0282
0.0282
29
RELAY MODULES WITH VALVE PROVING
Lookup Table
12
13
14
Test Time = 187,000 x (P x X ÷ C)
Test Time = 187,000 x (2 x 0.0893 ÷ 2500) = 13.4
seconds.
Round up to 14 seconds; enter 14 seconds into the VPS
Setup.
V48
V5055
0.0010
0.0046
0.0010
0.0046
0.0035
0.0046
0.0035
0.0218
0.0048
0.0218
0.0048
0.0227
0.0048
0.0227
0.0779
V48
V5055
0.0048
0.0067
0.0048
0.0067
0.0110
0.0067
0.0110
0.0238
0.0184
0.0238
0.0184
0.0245
0.0184
0.0245
0.0801
Results
Formula Item
0.0218
V1
0.0267
V2
3.356
A
1.75
L
2
P
2500
C
V5097A1004 V5097A1012
0.0066
0.0066
0.0066
0.0066
0.0066
0.0285
0.0285
0.0285
V5097A1004 V5097A1012
0.0093
0.0093
0.0093
0.0093
0.0093
0.0303
0.0303
0.0303