Panasonic 4466 Technical Description page 27

External power supply
Table of Contents

Advertisement

4466 EXTERNAL POWER SUPPLY - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
12. TECHNICAL DATA
All current consumptions are valid by nominal voltage and by 25 °C.
Voltage:
Primary
COM Loop Voltage
Allowed
Normal
COM Loop Current:
Quiescent
Active
Board 4467 current consumption
Mains OK output
Voltage outputs:
Normal
By battery backup
Maximum current per output
Maximum Total current:
Continuous
When fire alarm is activated in the system
Batteries
Inside the housing (two batteries)
Outside the housing
Address range
Address setting
Short circuit isolator
Internal battery
Material
Ambient temperature:
Operating
Storage
Ambient humidity
Ingress protection rating
Size:
H x W x D
Weight (including batteries):
Colour
230V AC
12 – 30V DC
24V DC
≤ 6 mA
≤ 6 mA
10.6 ± 2 mA @24.0 V
Normally low
24 V DC
16-29.5
V DC
2.0 A
3.0 A alternative 1.5 A (low or high charging mode)
4 A
≤ 7.2 Ah, L x W x H: 151 x 64.5 x 94 mm
≤ 42 Ah
001-253
Auto addressing (or with address setting tool)
Yes
Yes
Metal housing
-5 to +40 °C
-20 to +70 °C
Maximum 95 % RH (Non condensing)
IP30
298 x 424 x 95 mm
4660 g (excluding batteries)
9660 g (including batteries)
Light grey (NCS S1500-N, PMS Cool Grey 2)