Limitation of Installation and AHU

Limitation of Installation and Application
Refer to Fig. 2.1 "System Overview (1)" and Fig. 2.2 "System Overview (2)" for the following symbols.
L1: the distance*
between the heat exchanger of AHU and the Expansion Valve for the piping length
1
H1: the height difference*
L2: the length*
of thermistor for Outlet Air/Inlet Air/Liquid Pipe/Gas Pipe
3
L3: the length*
of control wires for electrical expansion valve
4
Ti:
the suction air temperature*
W2: the total AHU capacity with DX-Kit to outdoor unit capacity*
W1: the total standard indoor unit capacity to outdoor unit capacity*
*
The distance must be 5m or less.
1
*
The difference must be 2m or less.
2
*
The length must be 10m or less.
3
*
The length must be 10m or less.
4
5
*
The temperature range must be:
Cooling: 21°CDB/15°CWB ~ 32°CDB/23°CWB
Heating: 15°CDB ~ 27°CDB
*
The capacity for Multi combination with AHU and standard indoor unit must be:
6
< W1+W2: More than 100 to 110% >
W2: maximum 30%
Allowable AHU capacity in a system: 2 to 6HP
< W1+W2: 50 to 100% >
W2: No Limitation
Allowable AHU capacity in a system: No Limitation
Minimum indoor unit capacity or AHU capacity:
Max. Capacity of Single AHU in
system
12 to 20 HP
22 to 30 HP
32 to 60 HP
62 to 90 HP
For Single combination with only AHU:
W2: maximum 50 to 100%.
P5417151-rev.1
between the heat exchanger of AHU and the Expansion Valve
2
just before the DX-coil.
5
Min. indoor unit capacity or
Min. AHU capacity in a system
6
6
0.8 HP
2.0 HP
4.0 HP
6.0 HP