Units Installation - Hitachi RPK-0.8FSNH2M Installation And Operation Manual

Indoor units system free wall type
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
2

2. UNITS INSTALLATION

¬
WARNING:
-
Check to ensure that the accessories are packed with
the indoor unit.
-
Do not install the indoor units outdoors. If installed
outdoors, an electric hazard or electric leakage will
occur.
-
Consider the air distribution from each indoor unit to
the space of the room, and select a suitable location
so that uniform air temperature in the room can be
obtained.
-
The installation height of indoor unit must be 2.3m or
more.
-
Pay attention to the following points when the indoor
units are installed in a hospital or other places where
there are electronic waves from medical equipment,
etc.
-
Do not install the indoor units where electromagnetic
wave is directly radiated to the electrical box, remote
control cable or remote control switch.
-
Prepare a steel box and install the remote control
switch in it. Prepare a steel conduit tube and wire the
remote control cable in it. Then connect the ground
wire with the box and tube.
-
Install a noise filter when the power supply emits
harmful noises..
-
The contact of silicon gas with heat exchanger fin
surface causes water leakage of drain water or
electrical trouble due to this leaked water.
-
This unit is exclusive non electrical heater type indoor
unit. It is prohibited to install a electrical heater in the
field.
-
Mount suspension bolts using M10 (W3/8) as size, as
shown below:
-
Do not put any foreign material into the indoor unit
and check to ensure that none exist in the indoor unit
before the installation and test running. Otherwise a
fire or failure, etc., may occur.
CAUTION:
-
Do not install the indoor units in a flammable
environment to avoid a fire or an explosion.
-
Check to ensure that the ceiling slab is strong
enough. If not strong enough, the indoor unit may fall
down on you.
-
Do not install the indoor units, outdoor unit, remote
control switch and cable within approximately 3
meters of strong electromagnetic wave radiators such
as medical equipment.
-
Do not install the indoor units in a machinery shop or
kitchen where vapor from oil or mist flows to the
indoor units. The oil will deposit on the heat
exchanger, thereby reducing the indoor unit
performance, and may deform. In the worst case, the
oil damages the plastic parts of the indoor unit.
-
To avoid any corrosive action to the heat exchangers,
do not install the indoor units in an acid or alkaline
environment.
-
When lifting or moving the indoor unit, use
appropriate slings to avoid damage and be careful not
to damage the insulation material on units surface.
-
Tighten the flare nuts with prescribed tightening
torque, information is prescribed in Outdoor Unit
manual. Tightening too much causes refrigerant
leaked.

Advertisement

Table of Contents
loading

Table of Contents