Download Print this page

Accessories - GE EntelliGuard G Application Manual

Power circuit breaker
Hide thumbs Also See for EntelliGuard G:

Advertisement

EntelliGuard G Power Circuit Breaker
Section 4. Accessories
Figure 4.1
Accessory Mounting
A wide range of optional accessories are interchange-
able across all EntelliGuard G power circuit breakers,
regardless of nominal rating or envelope/frame size.
Each one incorporates easy-fit design features for
quick installation, either at the factory or in the field.
NOTE: When ordering REPLACEMENT accessories,
add "R" to the end of the catalog number shown.
Table 4.1
Motor Operators
Envelope Power Consumption Nominal Control Voltage IEC Range (85%-110%) ANSI Range UL Range (85-110%) Cat. No.
DC - 300W
1
AC - 350VA
DC - 480W
2 & 3
AC - 560VA
Courtesy of NationalSwitchgear.com
24 /30 Vdc
20.4V-26.4V
48 Vdc
40.8V-52.87V
60 Vdc
51V-66V
72 Vdc
61.2V-79.2V
110/130 Vdc
106.25V-137.5
250 Vdc
212.5V-275V
48 Vac
40.8V-52.87V
120 Vac
102V-132V
240 Vac
204V-264V
277 Vac
235.5V-304.7V
346 Vac
380/400 Vac
323V-440V
440 Vac
374V-528V
24 /30 Vdc
20.4V-26.4V
48 Vdc
40.8V-52.87V
60 Vdc
51V-66V
72 Vdc
61.2V-79.2V
110/130 Vdc
106.25V-137.5
250 Vdc
212.5V-275V
48 Vac
40.8V-52.87V
120 Vac
102V-132V
240 Vac
204V-264V
277 Vac
235.5V-304.7V
346 Vac
380/400 Vac
323V-440V
440 Vac
374V-528V
Motorized Spring Charging Unit
The unique motor/gearbox unit is specially designed
to operate with the full range of EntelliGuard G. It
is easily fitted with three heavy-duty bolts. After a
breaker close operation, the unit automatically
recharges the spring and makes it ready for
immediate open and re-close should the need arise.
High speed recharging ensures that the springs are
fully charged within approximately three seconds
following a release. All electrically operated (EO)
ANSI/UL breakers are equipped with "Spring Charged"
contacts for status indication. See Table 4.1.
Duty Cycle
2 / Minute
Spring Charge Time
3 Seconds Max
Circuit Breaker Closing Coil
The closing coil is an easy-to-fit, clip-on unit with
simple plug-in connectors. This permits either local
or remote release of the spring charged closing
mechanism by electrical operation. The standard
anti-pumping safety feature ensures that the
-
20.4V-26.4V
38V-56V
40.8V-52.87V
-
51V-66V
-
61.2V-79.2V
100V-140V
106.25V-137.5
200V-280V
212.5V-275V
-
40.8V-52.87V
104V-127V
102V-132V
208V-254V
204V-264V
235.5V-304.7V
-
323V-440V
-
374V-528V
-
20.4V-26.4V
38V-56V
40.8V-52.87V
-
51V-66V
-
61.2V-79.2V
100V-140V
106.25V-137.5
200V-280V
212.5V-275V
-
40.8V-52.87V
104V-127V
102V-132V
208V-254V
204V-264V
235.5V-304.7V
-
323V-440V
-
374V-528V
GMO124D
GMO1048D
GMO1060D
GMO1072D
GMO1130D
GMO1250D
GMO1048A
GMO1120A
GMO1240A
GMO1277A
GMO1346A
GMO1400A
GMO1440A
GMO224D
GMO2048D
GMO2060D
GMO2072D
GMO2130D
GMO2250D
GMO2048A
GMO2120A
GMO2240A
GMO2277A
GMO2346A
GMO2400A
GMO2440A
31