Zennio KNX ZRX-KCI4SO Technical Documentation

Knx consumption interface

Advertisement

Quick Links

KNX Consumption Interface
ZRX-KCI4SO
FEATURES
 4 channels for consumption counters (meters) with S0-pulse
outputs (UNE-EN 62053-31) *.
 Registration of consumed electric power, cost and CO
that can be split in up to 4 time intervals.
 Compliant with UNE-EN 62053-31 Class B.
 Total data saving on KNX bus power failure.
 KNX BCU integrated.
 Size 90 x 60 x 35 mm (2 DIN units).
 DIN rail unit assembly (EN 50022), with snap fit clamp.
 CE directives compliant.
*Other counters (meters) with dry-voltage output or not complying S0 standard
may also work (previous test is recommended)
1. Battery holder
5. Programming LED
Programming button: short button press to set the programming mode. If this button is held while plugging the device into the KNX bus, it goes into
safe mode.
Programming LED: programming mode indicator (red). When the device goes into safe mode, it blinks (red) every half second.
LOW batt. LED: if this LED is blinking in red, replace the batteries as soon as possible.
EMPTY batt. LED: if this LED is blinking in red, the batteries are empty.
GENERAL SYSTEM SPECIFICATIONS
Concept
Type of device
Voltage
Voltage range
KNX
Max
Supply
consumption
Bus connection
Battery (auxiliary power supply)
Working temperature
Storage temperature
Ambient humidity (relative)
Storage humidity (relative)
Complementary characteristics
Safety class
Operation type
Device action type
Electrical stress period
Degree of protection
Assembly
Minimum clearances
KNX bus failure response
Response when restarting KNX bus
Operation indication
Weight
PCB CTI index
Housing material
(1)
Maximum consumption in the worst case scenario (KNX Fan-In model)
Technical Documentation
© Zennio Avance y Tecnología S.L.
2. EMPTY batt. LED indicator
6. Input Indicator LED
Description
Electric operation control device
29VDC SELV
21...31VDC
Voltage
29VDC (typical)
(1)
24VDC
Typical bus connector TP1; 0.80mm² section
2 CR2032 battery (2 x 3V). It allows to keep counting pulses without the KNX bus
power supply
from 0ºC to +45ºC
from -20ºC to +70ºC
30% to 85% RH (no condensation)
30% to 85% RH (no condensation)
Class B
III
Continuous operation
Type 1
Long
IP20, clean environment
Independent device to be mounted inside electrical panels with DIN rail (EN 50022)
Not required
Data saving according to parameterization
Data recovering according to parameterization
Programming LED indicates programming mode (red) or safe mode (blinking red).
LOW and EMPTY batt. LED indicate the battery level when blinking in red (KNX
supply necessary). LED input indicator blinks when a pulse is received
95g including batteries (89g without batteries)
175V
PC FR V0 halogen free
Edition 4
emissions
2
3
4
5
6
7
3. LOW batt. LED indicator
7. Input connectors
mA
12.5
15
Further information
Technical Documentation
1
Figure 1: KNX Consumption Interface
4. Programming button
8. KNX connector
mW
363
360
www.zennio.com
KCI
2
8
Page 1 / 2

Advertisement

loading

Summary of Contents for Zennio KNX ZRX-KCI4SO

  • Page 1 95g including batteries (89g without batteries) PCB CTI index 175V Housing material PC FR V0 halogen free Maximum consumption in the worst case scenario (KNX Fan-In model) Technical Documentation Page 1 / 2 © Zennio Avance y Tecnología S.L. Edition 4 Further information www.zennio.com...
  • Page 2 Once the device is installed, the terminals should not be accessible.  The WEEE logo means that this device contains electronic parts and it must be discarded properly following the instructions of http://zennio.com/weee-regulation Technical Documentation Page 2 / 2 © Zennio Avance y Tecnología S.L. Edition 4 Further information www.zennio.com...