CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
Connection to a CP-IO Bus Powered by the Separate Transformer
CPO-PC400-W/CPO-PC400-UW
Isola on
Barrier
GND_ISO
GND
RX
RS485-
TX
RS485+
5V
5V_ISO
NOTES:
N = max. 16 CP-EXPIO modules or 16 CP-DIO modules (or a mixture thereof). The mode switch of the inte-
grated termination resistor of the final CP-DIO (CP-DIO #N) must be set to "ON." The CP-EXPIO module sup-
ports the addressing from address 0 to 15. Therefore, it supports 16 modules per channel. If the last module is
CP-EXPIO, the end of line resistor must be included.
For communication cable lengths, transmission speeds, and termination, see "General Information on the
RS485 Standard" section on page 7. For capacity restrictions, see "Connection to CP-IO Bus" section on
page 10. For fusing, see "Fusing" section on page 11.
EN0B-0085 IE10 R0420
110VAC/230VAC
24VAC
110VAC/230VAC
F1
F2
*
~
*
0
FGND
GND
-
R
T
+
Fig. 21. Connection (L > 3 m) of RS485 interface 4 to a CP-IO Bus
CP-DIO/EXPIO #1
24VAC
L > 3m
30
CP-DIO/EXPIO #N
R
T