Honeywell ComfortPoint Open CPO-PC400-W Manual page 29

Hvac controller
Table of Contents

Advertisement

Connection to Modbus devices with non-isolated RS485 interfaces
R
T
5V_ISO
GND_ISO
Isola on
Barrier
5V
RX
TX
GND
CPO-PC400-W/CPO-PC400-UW
Fig. 20. Connection (L > 3 m) of RS485 interfaces 1, 2, or 3 (RS485 interface 1 shown) to a Modbus
NOTES:
N = max. 30 unit loads. Always power the CPO-PC400-W/CPO-PC400-UW and connected Modbus modules
with separate transformers. Termination resistors must be inserted directly into the terminals of the individual
Modbus modules.
Signal ground (signal reference) connection is recommended. For more information, see "General Information
on the RS485 Standard" section on page 7.
For communication cable lengths, transmission speeds, and termination, see "General Information on the
RS485 Standard" section on page 7. For fusing, see "Fusing" section on page 11.
110VAC/230VAC
24VAC
F1
29
CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
L > 3m
Modbus
Module #1
Modbus
Module #N
R
T
EN0B-0085 IE10 R0420