Installation Position Of Units And Access Time; Restrictions On Configuration Capacity - Panasonic FP7 Series User Manual

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

1.3 Restrictions on Using Expansion Unit

1.3.3 Installation Position of Units and Access Time

Restrictions on installation position of units
● There is no restriction on the installation position of each unit in FP7 series. However, the
access time to the units installed in the expansion block is longer than that to the units
installed in the base block as shown in the table below, and it affects the scan time.
● When large-volume data access is assumed with a communication system unit, a unit in
which interrupt occurs or user programs, it is recommended to install the target units in the
base block. It enables to decrease the scan time relatively.
Difference in access time between installation positions of units
Installation
position
Base block
Expansion block
(Short distance
mode)
Expansion block
(Long distance
mode)
(Note 1)
The values in the above table indicate each time the CPU unit accesses the units installed in each
block via bus in I/O refresh processing or operation processing. The scan time with operation
processing time and base time added can be confirmed in the "status display" dialog box of the tool
software.

1.3.4 Restrictions on Configuration Capacity

Unit configuration capacity
● If units in which a lot of configuration data are set such as a positioning unit are used in the
expansion block a lot, the configuration capacity may exceed the capacity that the CPU unit
can handle.
● Check the configuration capacity in the "I/O map setting" dialog box of the tool software in
advance.
● The configuration capacity varies according to the functions and settings used in each unit.
Also, the maximum registration capacity to be assigned depends on the number of installed
expansion units.
1-10
Access time
Time per word
0.47 μs/word
2.5 μs/word
4.1 μs/word
Remarks
Ratio to base
block
1 time
The total length of expansion cabels is 9 m or
less.
5.3 times
The LED "SP0" on the expansion master unit
turns on.
The total length of expansion cabels is 10 m
to 30 m.
8.7 times
The LED "SP1" on the expansion master unit
turns on.
WUME-FP7CPUH-09

Advertisement

Table of Contents
loading

Table of Contents