1.2 Overview of Functions

1.2 Overview of Functions

1.2.1 Overview of Logging Function

Overview
● The logging function is used to record arbitrary contacts and data information together with
time stamp information at any time, and save them in an SD memory card inserted in the
CPU unit.
● Log data is saved as csv format files.
● Use the Logging/Trace Settings menu of the tool software FPWIN GR7 to set the
conditions.
● The settings are downloaded to the PLC as a part of project data, and stored in the ROM1.
The setting data can be saved in SD memory cards and used.
● The logging operation is executed by any of these operations: (1) tool software FPWINGR7,
(2) dedicated instructions or (3) Autostart via setting.
● To perform data logging at high speed, the buffer memory in the CPU unit is used.
Specifications
Item
Max. number of records
Number of file
generations
Number of logs
Buffer memory
Logging start-stop
Logging trigger condition
File determination
condition
(Logging stop trigger
condition)
File format
(Note 1)
Logging is executed when the condition is met at the end of scan.
(Note 2)
Use it together with the (DF) instruction to turn ON only for one scan.
1-4
Specifications
1,000,000 records
Max. 2,000 generations / 1 log
Max. 500 devices (500 to 2,000 words) / 1 record
Max. 1M words
Can be divided into max. 16 (LOG0 to LOG15) areas
for use.
Capacity per division: 8k words to 1M words
Selectable from the tool software, instructions or
autostart.
(Note 1)
Bit device ON
Cycle: Hour, minute, second
Time: Per minute, Per hour, Every day, Every week,
Every month, Every year
Instruction: Executes an instruction with an arbitrary
condition and starts logging.
(Note 2)
Bit device ON
Time: Per minute, Per hour, Every day, Every week,
Every month, Every year
Max. number of records
Data is saved in csv format.
Remarks
Shared with the trace
function.
Arbitrary comments can be
given.
The upper limit of the
capacity on the file system is
4 GB.
WUME-FP7CPULOG-04