Write Protect Jumper on Foundation Fieldbus (FF)

On Foundation Fieldbus transmitters there is no Failsafe jumper selection but there is a
Write Protect jumper.
The bottom jumper sets the Write Protect. The default setting is OFF (Un-protected).
When set to the On (Protected) position, changed configuration parameters cannot be
written to the transmitter.
When set to the OFF (Un-protected) position, changed configuration parameters can be
written to the transmitter.
Fieldbus not applicable to STT750
ATTENTION: Electrostatic Discharge (ESD) hazards. Observe
precautions for handling electrostatic sensitive devices.
WARNING! PERSONAL INJURY: Risk of electrical shock. Disconnect
power before proceeding. HAZARDOUS LIVE voltages greater than
30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible. Failure to
comply with these instructions could result in death or serious injury.
Step
1
Turn OFF Transmitter power.
Loosen the end-cap lock, and unscrew the end cap from the
2
Electronics side of the Transmitter housing.
If applicable, carefully depress the tabs on the sides of the Display
Module and pull it off. If necessary, move the interface connector from
3
the Communication Module to the display module to provide the
preferred orientation of the display module in the window.
Set the Write Protect jumper (Bottom jumper) to the desired behavior
4
(Protected or Unprotected). See
Screw on the end cap and tighten the end-cap lock.
5
Turn ON Transmitter power.
6
Image
Figure 17: Fieldbus Write Protect
A3. Hazardous Locations Certifications
AGENCY
TYPE OF PROTECTION
Explosion proof,
Certificate:
FM16US0157X:
Class I, Division 1,
Groups A, B, C, D;
Dust Ignition Proof:
Class II, III, Division 1,
Groups E, F, G; T6..T5
Class 1, Zone 1, AEx d IIC
T6..T5 Gb
Class 2, Zone 21, AEx tb
o
IIIC T 95
C IP 66 Db
Intrinsically Safe,
Certificate:
FM16US0157X:
Class I, II, III, Division 1,
Groups A, B, C,
D, E, F, G; T4
FM
TM
Class I Zone 0 AEx ia IIC
Approvals
T4 Ga
(USA)
FISCO Field Device (Only
for FF Option)
Ex ia IIC T4
Non-Incendive,
Certificate:
FM16US0157X:
Class I, Division 2,
Groups A, B, C, D; T4
Class I Zone 2 AEx nA IIC
T4 Gc
AEx nA IIC T4
Standards: FM 3600:2011; ANSI/ ISA 60079-0: 2013
FM 3615:2006; ANSI/ ISA 60079-1 : 2015
FM 3616 : 2011 ; ANSI/ ISA 60079-31 : 2015
FM 3610:2010; ANSI/ ISA 60079-11 : 2014
FM 3810 : 2005 ; FM 3611:2004; ANSI/ ISA 60079-15 : 2012 ;
FM 3810 : 2005 ; NEMA 250 : 2003 ; ANSI/ IEC 60529 : 2004
Enclosure: Type 4X/
IP66/ IP67
Action
Figure 17
for jumper positioning.
Description
Fieldbus SIM Mode = OFF
Write Protect = OFF (Not Protected)
Fieldbus SIM Mode = OFF
Write Protect = ON (Protected)
Fieldbus SIM Mode = ON
Write Protect = OFF (Not Protected)
COMM
Electrical
Ambient
OPTION
Parameters
Temperature
o
T5: Ta= -50
C
4-20 mA/
to 85
o
C
o
DE/HART/
T6: Ta= -50
C
Note 1
o
FF/
to 65
C
PROFIBUS
4-20 mA/
o
o
-50
C to 70
C
DE/HART
Note 2
/FF/
PROFIBUS
4-20 mA/
o
o
DE/HART
-50
C to 85
C
Note 1
/FF/
PROFIBUS
ALL
ALL
ALL
STT850/750 Quick Start Guide
Appendix A. PRODUCT CERTIFICATIONS
A1. Safety Instrumented Systems (SIS) Installations
For Safety Certified Installations, please refer to STT850/750 Safety Manual
#34-TT-25-05 for installation procedure and system requirements.
A2. European Directive Information (EU)
https://www.honeywellprocess.com/library/support/Public/Documents/
50094560.pdf
Explosion proof, Certificate:
2689056:
Class I, Division 1, Groups A, B,
C, D;
Dust Ignition Proof:
Class II, III, Division 1, Groups
E, F, G; T4
Zone 1 Ex d IIC T4 Gb
o
Ex tb IIIC T 95
C IP 66 Db
DIP A21 Class II, III
Intrinsically Safe, Certificate:
2689056:
Class I, II, III, Division 1, Groups
A, B, C, D, E, F, G; T4
Ex ia IIC T4 Ga
FISCO Field Device (Only for FF
Option)
Ex ia IIC T4
Non-Incendive, Certificate:
2689056:
CSA-
Class I, Division 2, Groups A, B,
Canada
C, D; T4
Class I Zone 2 Ex nA IIC T4 Gc
Ex nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
Standards:
CSA C22.2 No. 0-10; CSA 22.2 No. 25-1966 (reaffirmed 2009);
CSA C22.2 No. 30-M1986 (reaffirmed 2012); CSA C22.2 No. 94-M91;
CSA C22.2 No. 142-M1987 (reaffirmed 2009); CSA-C22.2No.157-92 (reaffirmed
2012);
C22.2 No. 213-M1987(reaffirmed 2012); C22.2 No. 60529-05
C22.2 No. CSA 60079-0:2011; C22.2 No. 60079-1: 2011; C22.2 No. 60079-11:
2011;
C22.2 No. 60079-15: 2012; C22.2 No. 60079-31: 2012;
ANSI/ ISA12.12.01-2012; ANSI/ ISA 60079-0 (12.00.01): 2009 ;
ANSI/ ISA 60079-1 (12.22.01): 2009 ; ANSI/ ISA 60079-11(12.02.01) : 2012;
ANSI/ ISA 60079-26 (12.00.03) : 2011; ANSI/ ISA 60079-15(12.12.02) : 2012 ;
ANSI/ ISA 60079-27 (12.02.04) : 2006; ANSI/ ISA 60079-31(12.10.03) : 2009 ;
FM Class 3615: Aug 2006; FM Class 3616: Dec 2011; ANSI/ IEC 60529 : Edition 2.1
ANSI/ UL 913: Edition 7; ANSI/ UL 916 : Edition 4 ;
o
T5: Ta= -50
C to
o
4-20 mA/
85
C
DE/HART/
Note 1
T6: Ta= -50
o
C to
FF
65
o
C
4-20 mA/
o
o
DE/HART/
Note 2
-50
C to 70
C
FF
4-20 mA/
o
o
DE/HART/
Note 1
-50
C to 85
C
FF
ALL
ALL
ALL
5